background image

Preparations and Precautions

Air and foreign matter in the refrigerant circuit can 

cause abnormal rises in pressure, which can damage 

the air conditioner, reduce its efficiency, and cause

injury. Use a vacuum pump and manifold gauge to 

evacuate the refrigerant circuit, removing any 

non-condensable gas and moisture from the system.      

Evacuation should be performed upon initial 

installation and when unit is relocated. 

BEFORE PERFORMING EVACUATION

  

Check to make sure the connective pipes

between the indoor and outdoor units

are connected properly .

  

Check to make sure all wiring is connected

properly.

Evacuation Instructions

Manifold Gauge

Compound 

gauge

-76cmHg

Low pressure 

valve

High pressure

valve

Pressure hose / 

Charge hose

Charge hose

V

acuum

pump

Pressure gauge

Low pressure valve

1.

 

Connect the charge hose of the manifold 

gauge to service port on the outdoor unit’s 

low pressure valve. 

Connect another charge hose from the 

manifold gauge to the vacuum pump. 

Open the Low Pressure side of the manifold 

gauge. Keep the High Pressure side closed. 

Turn on the vacuum pump to evacuate the 

system.

Run the vacuum for at least 15 minutes, or

until the Compound Meter reads -76cmHG

(-10

5

Pa).    

  

2.

 

3.

4.

 

5.

6.

Close the Low Pressure side of the manifold

gauge, and turn off the vacuum pump.

7.

Wait for 5 minutes, then check that there

has been no change in system pressure.

8.

If there is a change in system pressure, refer

to Gas Leak Check section for information

on how to check for leaks. If there is no

change in system pressure, unscrew the cap

from the packed valve (high pressure valve).

9.

Insert hexagonal wrench into the packed valve

(high pressure valve) and open the valve by

turning the wrench in a 1/4 counterclockwise

turn. Listen for gas to exit the system, then

close the valve after 5 seconds.

10.

Watch the Pressure Gauge for one minute

to make sure that there is no change in

pressure. The Pressure Gauge should read

slightly higher than atmospheric pressure.

Flare nut

Cap

valve body

valve stem

11.

Remove the charge hose from the service port.

12.

Using hexagonal wrench, fully open both the

high pressure and low pressure valves.

13.

Tighten valve caps on all three valves (service

port, high pressure, low pressure) by hand.

You may tighten it further using a torque

wrench if needed.

 OPEN VALVE STEMS GENTLY

When opening valve stems, turn the hexagonal 

wrench until it hits against the stopper. Do not 

try to force the valve to open further.

Air Evacuation

Air Evacuation

Page 37

Summary of Contents for KPDA-35 DVR14

Page 1: ...4 Duct OWNER S INSTALLATION MANUAL IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference Please che...

Page 2: ...Unit Specifications and Features 08 Owner s Manual Table of Contents Safety Precautions 04 Care and Maintenance 11 Troubleshooting 13 1 Indoor unit 08 2 Operating temperature 09 3 Other features 10...

Page 3: ...g 34 2 Indoor Uint Wiring 34 3 Power Specifications 35 3 Anchor outdoor unit 27 Refrigerant Piping Connection 29 A Note on Pipe Length 29 B Connection Instructions Refrigerant Piping 30 1 Cut pipe 30...

Page 4: ...must be supervised around the unit at all times operate your air conditioner in a wet room such as a bathroom or laundry room Too much exposure to water can cause electrical components to short circui...

Page 5: ...residual current device RCD having a rated residual operating current not exceeding 30mA and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules For all electric...

Page 6: ...stall the unit in a location that may be exposed to combustible gas leaks If combustible gas accumulates around the unit it may cause fire Do not turn on the power until all work has been completed Wh...

Page 7: ...14903 Amount of refrigerant to be charged kg Minimum room area m 1 11 1 1 65 2 2 58 5 3 08 7 3 84 10 4 24 Model Btu h 12000 18000 24000 30000 36000 42000 48000 12 4 39 60000 13 Safety Precautions Pag...

Page 8: ...control has been misplaced or is out of batteries Air outlet Air inlet Air filter on some models Drain hose Electric control cabinet Refrigerant connecting pipe A For the unit which the filter is remo...

Page 9: ...owing temperature ranges certain safety protection features may activate and cause the unit to disable COOL mode HEAT mode DRY mode Room Temperature 17 C 32 C 0 C 30 C 10 C 32 C Outdoor Temperature 0...

Page 10: ...will automatically return to the previous position The angle of the horizontal louver should not be set too small as condensation may form and drip into the machine To reset the louver press the manu...

Page 11: ...conditioner can reduce the cooling efficiency of your unit and can also be bad for your health Make sure to clean the filter once every two weeks WARNING DO NOT REMOVE OR CLEAN THE FILTER BY YOURSELF...

Page 12: ...outlets If using a vacuum cleaner the inlet side should face the vacuum If using water the inlet side should face down and away from the water stream CAUTION Before changing the filter or cleaning tur...

Page 13: ...ion of the unit s plastic parts Both the indoor unit and outdoor unit make noises Low hissing sound during operation This is normal and is caused by refrigerant gas flowing through both indoor and out...

Page 14: ...description of the unit malfunction as well as your model number Troubleshooting When troubles occur please check the following points before contacting a repair company Problem Possible Causes Solut...

Page 15: ...Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use Low refrigerant due to leak or long term use Check for leaks re...

Page 16: ...ctor 12 7 15 9 some models Transfer connector 6 35 9 52 some models Transfer connector 9 52 12 7 some models Connecting wire for display 2m some models Cord protection rubber ring some models Display...

Page 17: ...ation Summary Install the outdoor unit Install the drainpipe 1 2 3 4 5 MC MC 6 Install the indoor unit Evacuate the refrigeration system Connect the wires Connect the refrigerant pipes 7 Installation...

Page 18: ...ent The actual shape shall prevail NOTE The installation must be performed in accordance with the requirement of local and national standards The installation may be slightly different in different ar...

Page 19: ...es such as cabinets Kitchens that use natural gas Areas with strong electromagnetic waves Areas that store flammable materials or gas Rooms with high humidity such as bathrooms or laundry rooms Enough...

Page 20: ...A B C 18K 210 8 3 674 26 5 880 34 6 24K 36K 249 9 8 774 30 5 1100 43 3 30K 36K 249 9 8 774 30 5 1360 53 5 36K 60K 300 11 8 874 34 4 1200 47 2 air outlet opening size D E F 136 5 4 706 27 8 600 23 6 1...

Page 21: ...and fit pipes and wires after you have finished installing the main body When choosing where to start determine the direction of the pipes to be drawn out Especially in cases where there is a ceiling...

Page 22: ...xternal duct static pressure 2 Install the canvas tie in between the body and duct 3 The air inlet and air outlet duct should be far enough apart enough to a avoid air passage short circuit 4 Connect...

Page 23: ...e and will help seal it when you finish the installation process CAUTION When drilling the wall hole make sure to avoid wires plumbing and other sensitive components Wall Indoor Outdoor 12mm 0 5 inch...

Page 24: ...h of the drain hose to the unit s outlet pipe Sheath the mouth of the hose and clip it firmly with a pipe clasp 39 59 1 1 5m 1 1 Lean over 1 50 Ceiling 39 59 7 9 20cm 21 7 55cm Lean over 1 50 1 1 5m 1...

Page 25: ...leaks from the joints 3 Turn off the air conditioner and put the cap back on 3 Pass the drain hose through the wall hole Make sure the water drains to a safe location where it will not cause water dam...

Page 26: ...build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Strong wind If the unit is frequently exposed to heavy rain or snow Build a shel...

Page 27: ...ee Fig B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain joint to red...

Page 28: ...403 15 87 946x810x410 37 24x31 9x16 14 673 26 5 403 15 87 952x1333x410 37 5x52 5x16 14 634 24 96 404 15 9 952x1333x415 37 5x52 5x16 34 634 24 96 404 15 9 845x702x363 33 27x27 6x14 3 540 21 26 350 13 8...

Page 29: ...Type of model Capacity Btu h Length of piping Maximum drop height EU frequency conversion Split Type 15K 25 82 10 32 8 15K 24K 30 98 4 20 65 6 24K 36K 50 164 25 82 36K 60K 65 213 30 98 4 Other Split...

Page 30: ...and flare them properly This will ensure efficient operation and minimize the need for future maintenance 1 Measure the distance between the indoor and outdoor units 2 Using a pipe cutter cut the pip...

Page 31: ...door unit tubing Flare nut Pipe 3 Tighten the flare nut as tightly as possible by hand 4 Using a spanner grip the nut on the unit tubing 5 While firmly gripping the nut use a torque wrench to tighten...

Page 32: ...Every wire must be firmly connected Loose wiring can cause the terminal to overheat resulting in product malfunction and possible fire 10 Do not let wires touch or rest against refrigerant tubing the...

Page 33: ...less than 16A the power cord of air conditioner shall be equipped with plug purchased seperately 12 To avoid getting an electric shock never touch the electrical components soon after the power supply...

Page 34: ...or metal parts 6 Reinstall the cover of the electric control box 1 Prepare the cable for connection a Using wire strippers strip the rubber jacket from both ends of the signal cable to reveal about 15...

Page 35: ...IRCUIT BREAKER FUSE A 25 20 32 25 50 40 70 55 70 60 MODEL Btu h 36K 37K 60K 36K 37K 60K POWER PHASE 3 Phase 3 Phase 3 Phase 3 Phase 380 420V 380 420V 208 240V 208 240V CIRCUIT BREAKER FUSE A 25 20 32...

Page 36: ...10 15 10 15 10 15 10 15 10 POWER outdoor PHASE 1 Phase 1 Phase 1 Phase 1 Phase 1 Phase 208 240V 208 240V 208 240V 208 240V 208 240V CIRCUIT BREAKER FUSE A 25 20 25 20 40 30 50 40 50 40 MODEL Btu h 36...

Page 37: ...nutes or until the Compound Meter reads 76cmHG 105 Pa 2 3 4 5 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that there has been no ch...

Page 38: ...16 The refrigerant should be charged from the service port on the outdoor unit s low pressure valve The additional refrigerant to be charged can be calculated using the following formula Liquid Side D...

Page 39: ...ered correctly d Ensure the indicators on the remote control and the display panel on the indoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see that th...

Page 40: ...and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the servic...

Page 41: ......

Page 42: ......

Page 43: ......

Page 44: ......

Reviews: