41
E
The connected power supply cable should be
secured with a wire clamp to prevent loosening,
as shown in the right figure.
L
N
①
Power supply cable system connection
Power supply cable system connection depends on the methods of communication between the indoor
unit and outdoor unit. For the HyperLink (M1M2) communication method, indoor units are allowed to have
independent power supplies. For other communication methods, indoor units should be provided with
uniform power supplies.
A
Indoor units are provided with independent power supplies*, which are wired as follows:
For HyperLink (M1M2) communication with independent power supply:
CN3
CN2
TO UP INDOOR UNIT
TO DOWN INDOOR UNIT
M1
M2
CN10
L1
La
Lx
L11
Lb
Ly
L21
Lc
L30
××
××
M1
M2
CN23
L
N
CN1
M1
M2
M1
M2
CN3
CN2
TO UP INDOOR UNIT
TO DOWN INDOOR UNIT
M1
M2
M1
M2
M1
M2
CN10
××
××
L
N
CN1
M1
M2
CN10
××
××
L
N
CN1
M1
M2
CN10
××
××
L
N
CN1
M1
M2
CN10
××
××
L
N
CN1
M1
M2
CN10
××
××
L
N
CN1
M1
M2
CN10
××
××
L
N
CN1
···
Indoor unit 22-28#
···
Indoor unit 12-19#
HyperLink repeater 2
Indoor unit 11#
Circuit
breaker
Power supply for indoor unit
Indoor unit 20#
Circuit breaker
Power supply for indoor unit
Indoor unit 21#
Circuit breaker
Power supply for indoor unit
Indoor unit 29#
Circuit breaker
Power supply for indoor unit
Indoor unit 30#
Circuit
breaker
Power supply for indoor unit
HyperLink repeater 1
···
Indoor unit 2-9#
Indoor unit 1#
Circuit breaker
Power supply for indoor unit
Master
outdoor unit
Indoor unit 10#
Circuit breaker
Power supply for indoor unit
Power supply cable
Communication wires
CAUTION
When the indoor units are provided with independent power supplies, the indoor units in the same refrigerant
system should be V8 indoor units*, and the communication between indoor units and outdoor unit adopts a
HyperLink (M1M2) with an independent power supply.
This connection method has the function of an independent power supply, so in the same refrigerant system, the
number of indoor units must not exceed 30 sets, and a maximum of only two repeaters may be installed*.
One repeater shall be added for every 10 indoor units or a communication wire length of 200m added.