48
MDV-S80WHN8(At) Q4
Cooling mode:
Information requirements for air-to-air conditioners
Model(s): MDV-S80WHN8(At)
Test matching indoor units form, no-duct: 1x MIH1x MIH45Q4N18
Outdoor side heat exchanger of air conditioner: air
Indoor side heat exchanger of air conditioner: air
Type: compressor driven
Driver of compressor: electric motor
Item
Symbol
Value
Unit
Item
Symbol
Value
Unit
Rated cooling capacity
P
rated,c
7.20
kW
Seasonal space cooling
energy efficiency
η
s,c
225.0
%
Declared cooling capacity for part load at given outdoor
temperatures Tj and indoor 27/19°C (dry/wet bulb)
Declared energy efficiency ratio or gas utilisation
efficiency
/auxiliary energy factor for part load at given outdoor
temperatures T
j
T
j
=+35°C
P
dc
7.20
kW
T
j
=+35°C
EER
d
3.23
--
T
j
=+30°C
P
dc
5.31
kW
T
j
=+30°C
EER
d
5.30
--
T
j
=+25°C
P
dc
3.41
kW
T
j
=+25°C
EER
d
8.50
--
T
j
=+20°C
P
dc
3.10
kW
T
j
=+20°C
EER
d
9.90
--
Degradation co-
efficient for air
conditioners(*)
C
dc
0.25
--
Power consumption in modes other than "active mode"
Off mode
P
OFF
0.028
kW
Crankcase heater mode
P
CK
0.002
kW
Thermosat-off mode
P
TO
0.035
kW
Standby mode
P
SB
0.028
kW
Other items
Capacity control
variable
For air-to-air air conditioner:
air flow rate, outdoor
measured
--
3800
m³/h
Sound power
level, outdoor
L
WA
66
dB
GWP of the refrigerant
675
kg CO
2 eq
(100years)
Contact details
(*)If C
dc
is not determined by measurement, then the default degradation coefficient of heat pumps shall be 0.25.
Where information relates to multi-split air conditioners, the test result and performance data may be obtained on the basis
of performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.