18
C8
Settings to turn on/off
operating indicator
00: Off
01
Select “On” and the operating indicator will show the ON/OFF state
of the indoor unit.
Select “Off” and the operating indicator will always be off regardless
if the indoor unit is on or off.
01: On
C9
1
Static pressure setting
of indoor unit
A5
2
:00/01/02/
03/04/05/06/07
/08/09/FF
H-DUCT
3
,
FAPU:
00/01/~/19/ FF
01
The indoor unit sets the selected corresponding static pressure.
Refer to the indoor unit for specific static pressure values. FF: initial
valu e is based on the indoor unit data read by the wired controller.
C10
1
Set the time delay to
stop the fan of the
indoor unit.
00/01/02/03 /FF
00
Parameter
00
01
02
03
FF
Value
Represents
4
Min
8
Min
12
Min
16
Min
Based on the dial
switches in the main
PCB of the indoor unit
C11
1
Indoor unit -
cold draft prevention
temperature settings
00/01/02/03 /FF
00
Parameter
00
01
02
03
FF
Common
Indoor Unit
15°C/
59°F
20°C/
68°F
24°C/
75° F
26°C/
79° F
Based on the dial
switches in the main
PCB of the indoor unit
FAPU
14°C/
57°F
12°C/
54°F
16°C/
61°F
18°C/
64°F
Based on the dial
switches in the main
PCB of the indoor unit
C12
1 and 4
Indoor unit
heating
temperature
compensation
setting
00/01/02/ 03/04/
FF
00
Parameter 00
01
02
03
04 FF
Value
Represents
6°C/
43°F
2°C/
36° F
4°C/
39°F
6°C/
43°F
0°C/
32°
F
Based on the
dial switches
in the main
PCB of the
indoor unit
C13
1 and 4
Indoor unit cooling
- Temperature
compensation setting
00/01/FF
00
Parameter 00
01
FF
Value
Represents 0°C/32°F
2°C/36°F
Based on the dial
switches in the
main PCB of the
indoor unit
C5
1
Fan speed setting in
wired controller
00: 3 fan speeds
02
Default is 7 fan speeds.
The bi-directional communication automatically
identifies 3 fan speeds or 7 fan speeds.
01: 4 fan speeds
02: 7 fan speeds
C6
Reserved
/
00
/
C7
Display indoor room
temperature
00: No
00
If “00” is selected, the wired controller will display the
setting temperature when the backlight is off. If “01”
is selected, the wired controller will display the room
temperature when the backlight is off.
01: Yes
Summary of Contents for KCT-03 SR
Page 31: ...28 MD18U 003BW 16117100001523 ...
Page 32: ......