3.1
HEAT MODE
Enable or disable the heating mode
1
0
1
1
/
3.2
t_T4_FRESH_H
The refresh time of climate related curves for heating
mode
0.5
0.5
6
0.5
hours
3.3
T4HMAX
The maximum ambient operating temperature for
heating mode
25
20
35
1
°C
3.4
T4HMIN
The minimum ambient operating temperature for
heating mode
-15
-25
15
1
°C
3.5
dT1SH
The temperature difference for starting the unit (T1)
5
2
10
1
°C
3.6
dTSH
The temperature difference for starting the unit (Ta)
2
1
10
1
°C
3.7
t_INTERVAL_H
The compressor start time interval
5
5
60
1
MIN
3.8
T1SETH1
The setting temperature 1 of climate related curves for
heating mode
35
25
60
1
°C
3.9
T1SETH2
The setting temperature 2 of climate related curves for
heating mode
28
25
60
1
°C
3.10
T4H1
The ambient temperature 1 of climate related curves for
heating mode
-5
-25
35
1
°C
3.11
T4H2
The ambient temperature 2 of climate related curves for
heating mode
7
-25
35
1
°C
3.12
ZONE1 H-EMISSION
The type of zone1 end for heating mode: 0=FCU(fan
coil unit), 1=RAD.(radiator), 2=FLH(floor heating)
1
0
2
1
/
3.13
ZONE2 H-EMISSION
The type of zone2 end for heating mode: 0=FCU(fan
coil unit), 1=RAD.(radiator), 2=FLH(floor heating)
2
0
2
1
/
3.14
t_DELAY_PUMP
the time that the compressor has run before starting the
pump.
2
2
20
0.5
MIN
4.1
T4AUTOCMIN
The minimum operating ambient temperature for cooling
in auto mode
25
20
29
1
°C
4.2
T4AUTOHMAX
The maximum operating ambient temperature for
heating in auto mode
17
10
17
1
°C
5.1
WATER FLOW TEMP.
Enable or disable the WATER FLOW
TEMP.:0=NON,1=YES
1
0
1
1
/
5.2
ROOM TEMP.
Enable or disable the ROOM TEMP.:0=NON,1=YES
0
0
1
1
/
5.3
DOUBLE ZONE
Enable or disable the ROOM THERMOSTAT DOUBLE
ZONE:0=NON,1=YES
0
0
1
1
/
6.1
ROOM THERMOSTAT
The style of room thermostat: 0=NON,1=MODE
SET,2=ONE ZONE,3=DOUBLE ZONE
0
0
3
1
/
7.1
dT1_IBH_ON
The temperature difference between T1S and T1 for
starting the backup heater.
5
2
10
1
°C
7.2
t_IBH_DELAY
The time that the compressor has run before the first
backup heater turns on
30
15
120
5
MIN
7.3
T4_IBH_ON
The ambient temperature for starting the backup heater
-5
-15
10
1
°C
7.4
dT1_AHS_ON
The temperature difference between T1S and T1B for
turning the additional heating source on
5
2
10
1
°C
7.5
t_AHS_DELAY
The time that the compressor has run before starting
the additional heating source
30
5
120
5
MIN
7.6
T4_AHS_ON
The ambient temperature for starting the additional
heating source
-5
-15
10
1
°C
8.1
T1S_H.A_H
The target outlet water temperature for space heating
when in holiday away mode
25
20
25
1
°C
8.2
T5S_H.A_DHW
The target outlet water temperature for domestic hot
water heating when in holiday away mode
25
20
25
1
°C
12.1
PREHEATING FOR
FLOOR T1S
The setting temperature of outlet water during first
preheating for floor
25
25
35
1
°C
12.3
t_FIRSTFH
The time last for preheating floor
72
48
96
12
HOUR
12.4
t_DRYUP
The day for warming up during floor drying up
8
4
15
1
DAY
12.5
t_HIGHPEAK
The continue days in high temperature during floor
drying up
5
3
7
1
DAY
12.6
t_DRYD
The day of dropping temperature during floor drying up
5
4
15
1
DAY