Coding
Assembly unit
Coding
Assembly unit
A
Outdoor unit
J
SV2: 2-way valve (field supply)
B
Solar energy kit (field supply)
K
SV1: 3-way valve for domestic hot water tank
(field supply)
C
User interface
L
Domestic hot water tank
D
Room thermostat (field supply)
M
Booster heater
E
Boiler (field supply)
N
Contactor
F
P_s: Solar pump (field supply)
O
Power supply
G
P_c: Mixing pump (field supply)
P
Backup heater
H
P_o: Outside circulation pump (field supply)
Q
Zone2 SV3(3-way valve)
I
P_d: DHW pump (field supply)
Item
Description
AC/DC
Required number of conductors Maximum running current
1
Solar energy kit signal cable
AC
2
200mA
2
User interface cable
AC
5
200mA
3
Room thermostat cable
AC
2 or 3
200mA(a)
4
Boiler control cable
/
2
200mA
5
Thenrmistor cable for T1B
DC
2
(b)
9
DHW pump control cable
AC
2
200mA(a)
10
2-way valve control cable
AC
2
200mA(a)
11
3-way valve control cable
AC
2 or 3
200mAC
12
Thermistor cable
DC
2
(b)
13
Booster heater control cable
AC
2
200mA(a)
15
Power supply cable for unit
AC
2+GND(1-Phase)
3+GND(3-Phase)
31A (1-Phase) 15A
(3-Phase)
16
Power supply cable for backup heater
AC
2+GND(1-Phase)
3+GND(3-Phase)
14A (1-Phase) 6A
(3-Phase)
(a) Minimum cable section AWG18 (0.75 mm
2
).
(b)The thermistor cable are delivered with the unit: if the current of the load is large, an AC contactor is needed.
1
2
4
5
7
8
9
10
3
6
1-phase 12~16kW
3-phase 12~16kW
Coding
Assembly unit
1
High voltage wire hole
2
Low voltage wire hole
3
High voltage wire hole
4
Compressor connection port W
5
Drainage pipe hole
6
Low voltage wire hole
7
Low voltage wire hole(backup)
8
Low voltage wire hole(backup)
9
Water inlet
10
Water outlet
40
41
NOTE
Please use H07RN-F for the power wire, all the cable are connect to high voltage except for thermistor cable and cable
for user interface.
● Equipment must be grounded.
● All high-voltage external load, if it is metal or a grounded port, must be grounded.
● All external load current is needed less than 0.2A, if the single load current is greater than 0.2A, the load must be
controlled through AC contactor.
● AHS1" "AHS2", "A1" "A2", "R1" "R1" and "DTF1" "DTF2" wiring terminal ports provide only the switch signal.
Please refer to image of 9.7.6 to get the ports position in the unit.
● Expansion valve E-Heating tape,Plate heat exchanger E-Heating tape and Flow switch E-Heating tape share a control
port.