Chapter 3 Operation Panel
20
Code
Parameter
Function
Explanation
Parameter Value
Factory
Setting
selection)
d0003
:
Shutdown , Closing X5 will FWD
motor instantly;
During running, closing
X5 will shut down motor instantly .
Shutdown, closing X6 will REV motor
instantly ; During running, closing X6 will
shut down motor instantly
Pr.031
Multi-function
input terminal
setting
(Multi-function
input 1)
d0000: Multiple speed command 1
d0001: Multiple speed command 2
d0002: Multiple speed command 3
d0003: Multiple speed command4
d0004: Jog Fwd command
d0005: Jog Rev command
d0006: External faulty reset
d0007: External fault,
Closing operation
failure
d0008: External Fault, Opening operation
failure
d0009: Up command/frequency UP
d00010: Down command/Frequency down
d0011
:
Jog command, X5 determines
direction
d0012
:
Counter function when pulse
frequency is lower than 500HZ
d0013
:
Counter reset function, clear
present data
d0014: Receive external sudden-stop
signal, can reset automatic
d0015
:
0 start function timer, multi-function
output action
d0016: X4 is the input terminal for A mode
(always close)
d0017: AUTO RUN/PLC
d0018:PAUSE for PLC
d0019: PID is valid, connect junction, start
PID
d0020:No function. Isolate the wrong
operation from outside terminals.
d0000
Pr.032
Multi-function
input 2
d0001
Summary of Contents for KD4000 Series
Page 5: ...Chapter 2 Installation and wiring 4 2 2 KD4000 4T 380V Series Installation Dimension...
Page 6: ...Chapter 2 Installation and wiring 5 2 3 KD4000 2S 220V basic wiring diagram...
Page 7: ...Chapter 2 Installation and wiring 6 2 4 SD4000 4T 380V basic wiring diagram...
Page 15: ...Chapter 3 Operation Panel 14 3 3 Please observe below steps to set parameters...