18
English
Interruptions in the advance pressure unit
are indicated through red LED at the control
unit of the advance pressure pump.
LED
glows
Display
Possible cause
Remedy
–
Spannungsausfall
Uhr stellen !
Power failure
Set clock !
Arret secteur
L'horloge placer
mancan. corrente
regoli l'orolog.
Power failure during operations
Check power supply; set clock
Interruptions in the advance pressure unit
LED glows
Possible cause
Remedy
Red LED
glows
Raw water supply has been interrupted
Check raw water supply and restart it
After removing the fault, press the "Reset" key
Specifications
Ambient temperature
°C
+1...+60
Storage temperature, min.
°C
–10...+70
Humidity, max.
% rel.
100
Supply voltage, plant
V/Hz
400/3~50Hz
Control media/ active carbon filter
V/Hz
prim.: 230/1~50,
sec.: 12/1~50
Dosing module
V/Hz
230/1~50/60
Electrical fuses
A
25
Electrical connection value
kW
6
Raw water temperature
°C
+2...+40
Inlet pressure of raw water
MPa
0,2...0,6
Output range
l/day
15000±15%
Drinking water output, max.
l/h
650
Dimensions (h x b x d)
WPC 600 SW
mm
1800 x 900 x 800
WPC 600 SW-A
mm
1800 x 1200 x 800
WPC 600 SW-AM
mm
1800 x 1200 x 800
Weight in delivered state (without filter fillings)
WPC 600 SW
kg
220
WPC 600 SW-A
kg
240
WPC 600 SW-AM
kg
260
Design base for salt content in raw water (at 15 °C)
ppm
35000
Maximum salt content in raw water
ppm
60000
Summary of Contents for WPC 600 CD
Page 2: ...2 ...
Page 12: ...12 Deutsch Rückseite Bleibt leer damit das Blatt herausgetrennt werden kann ...
Page 22: ...22 English Rear side Is kept blank so that the sheet can be separated ...
Page 32: ...32 Français Verso Reste vide afin que la feuille peut être retirer ...
Page 42: ...Italiano 42 Tergo Resta vuoto in modo da poter separare il foglio ...
Page 52: ...52 Español Parte posterior En blanco para separar la hoja ...
Page 62: ...62 Ελληνικά Οπισθόφυλλο Παραμένει κενό για να αποκοπεί το φύλλο ...
Page 72: ...72 Türkçe Arka sayfa Sayfanın ayrılabilmesi için boş kalır ...