ECHNICAL SPECIFICATION
Environment
Ambient Temperature Range
-25 to +55 degrees Celsius
Dust and water rating
IP65
Compass safe distance
minimum 50 mm
Power related specification
Input voltage main and emergency battery
12/24 VDC +/- 30%
Maximum power usage
1 Watt quiescent 5 Watt in alarm
Maximum contact rate relays
30 VDC/1A
Voltage fire zone
15 Vdc
Limited alarm current fire detectors
60 mA
Sounder / beacon voltage main powered mode
18
–
22 VDC
Sounder / beacon alarm maximum current
100 mA
Connector and cable specification
Conductor cross section solid (Cross Sectional Area mm²)
0.5 mm² ... 1.5 mm²
Conductor cross section flexible (Cross Sectional Area mm²)
0.5 mm² ... 1.5 mm²
Conductor cross section AWG
20 ... 16
Stripping length
8 mm
Aerosol extinguisher output specification
Maximum Stat-X extinguisher count
5 connected on NETB 5 max 125 meters cable
Maximum Stat-X extinguisher count
10 connected on NETB 10 max 125 meters cable
Extinguisher release current
1,3A
Extinguisher release pulse length
25 ms
Solenoid extinguisher output specification
End of line component
2 x back - EMF diodes 1N4004 or equal
Maximum number solenoids
1
Maximum coil resistance
25 to 200 ohms
Maximum current
1 A
Voltage
24Vdc
Extinguisher release pulse length
8 seconds
Detection zone, hold and extinguishing release inputs
Normal state
> 8 kΩ < 12 kΩ
Alarm load
< 100
Ω >1.2 kΩ
Zone fault threshold 1
< 100
Ω
Zone fault threshold 2
> 1.2 k
Ω < 8 kΩ
Zone fault threshold 3
>
12 kΩ
Alarm resistant
470
Ω
End of line resistant
10 k
Ω