![K&G GROEP NANO MARINE Installation And Operation Manual Download Page 13](http://html2.mh-extra.com/html/kandg-groep/nano-marine/nano-marine_installation-and-operation-manual_3057869013.webp)
www.kg-groep.com P 13
16
DIP
S
WITCHES
16.1
S
ETTINGS
Standard setting ex factory, all PDS in OFF position.
▪
Automatic fire detector as the initiators of an extinguishing
action is the standard, no override the delay timer.
▪
The vehicle mode is disabled
▪
Activation of electrical igniters for aerosol fire extinguishers
▪
Dual zone alarm for automatic extinguishing release.
▪
VFC relay activate at 2
nd
fire alarm
▪
Extinguishant release delay 0 seconds
Recommended setting for marine application with manual release only:
▪
Front NCP manual release ONLY, fire detectors are not in use (PDS 1 OFF)
▪
The vehicle mode is disabled is not in use (PDS 2 OFF)
▪
Activation of electrical igniters for aerosol fire extinguishers (PDS 3 OFF)
▪
Dual zone alarm is not in use (PDS 4 OFF)
▪
VFC relay activate at 1
st
(PDS 5 ON)
▪
Extinguishant release 20 seconds (PDS 6 ON - PDS 7 OFF
–
PDS 8 OFF)
16.2
D
IRECT RELEASE
(PDS
1)
If a fire alarm is detected, by the automatic fire detectors the countdown
timer is started, you can override the timer when press the manual release.
PDS 1 OFF = extinguishing delayed also in manual operation if a delay has
been programmed.
PDS 1 ON = extinguishing without delay in manual operation.
16.3
V
EHICLE MODE
(PDS
2)
If the extinguishing system is intended to protect the engine compartment
of a vehicle, a programmed extinguishing delay must be disabled when the
vehicle is parked, and the driver leaves the vehicle.
PDS 2 OFF = system behaves as programmed with delay.
PDS 2 ON = delayed extinguishing is disabled when parked.
16.4
E
XTINGUISHING RELEASE OUTPUT
(PDS
3)
The NMS is equipped with two activation techniques for the activation of
fire extinguishing systems. Standard (PDS3OFF) on the NCP is programmed
for the activation of electrical igniters intended for aerosol fire
extinguisher units. When PDS 3 is set to the ON position, the NMS is
suitable for activating an extinguishing system using a solenoid
PDS 3 OFF = system is suitable for electrical igniters intended for aerosol fire extinguishers 1,3A/50ms
PDS 3 ON = system is suitable for solenoid activation 24V DC 1 A
WARNING
When the PDS 3 is in the ON position (solenoid only) DO NOT USE it in combination with an NETB.
This may cause irreparably damage to the ETB
’s
and the NCP.
ON
8
7
6
5
4
3
2
1
OFF
VEHICLE MODE ON
8
7
6
5
4
3
2
1
VEHIICLE MODE OFF
ON
8
7
6
5
4
3
2
1
OFF
8
7
6
5
4
3
2
1
AEROSOL SYSTEM ACTIVATION
SOLENOID SYSTEM ACTIVATION