Venkon XL
Assembly, installation and operating instructions
60
Parameter
Function
Standard
Min.
Max.
Unit
Venkon XL*
P038
Lock/disable function on the control unit
72
0
255
-
72
P039
Function of digital output V2 (in a 2-pipe system)
0
0
3
-
0
P040
Valve control by pulse width modulation
0
0
1
-
0
P041
Reset time of PI controller to activate the fan in automatic
fan mode
0
0
20
min.
0
P042
Fan setting: lock and activate fan stages
0
0
127
-
2
P043
Function of digital input DI1
0
0
22
-
12
P044
Function of digital input DI2
0
0
22
-
0
P045
Threshold voltage for potentiometer to switch on the unit
10
0
100
kiloohm
10
P046
Temperature setting corresponds to the minimum resist-
ance value = 10 kiloohm in the potentiometer
18
12
34
°C
18
P047
Temperature setting corresponds to the maximum resist-
ance value = 100 kiloohm in the potentiometer
24
13
35
°C
24
P048
Threshold voltage for potentiometer for starting up the
fans
10
0
100
kiloohm
10
P049
Threshold voltage for potentiometer for maximum fan
speed
90
0
100
kiloohm
90
P050
Fan setting: max. fan speed
100
0
100
%
100
P051
Fan setting: min. fan speed
0
0
90
%
15
P052
Fan setting: activation of fan speed limit
0
0
1
-
1
P053
Valve activation by pulse width modulation of the valve
switching cycle
15
10
30
min.
15
P054
Configuration of bus system
0
0
2
-
0
P055
Display of heating/cooling symbols in automatic mode
0
0
1
-
1
P056
DI2 setting (polarity) when DIP 4 = ON
1
0
1
-
1
P057
Reset setpoint to the value of P01 (after changing an oper-
ating program)
0
0
1
-
0
P058
Sensor adjustment: sensor AI1
0
-99
127
K/10
0
P059
Supply air temperature setpoint in heating mode
35
0
50
°C
35
P060
Supply air temperature setpoint in cooling mode
18
0
50
°C
18
P061
Sensor adjustment: sensor in the KaController
0
-99
127
K/10
0
P062
Sensor adjustment: sensor AI2
0
-99
127
K/10
0
P063
Outside temperature <P63 fan increase by P122
0
-99
127
°C
0
P064
Sensor adjustment: sensor AI3
0
-99
127
K/10
0
P065
reserved
-
-
-
-
-
P066
Master/slave assignment in CAN bus
0
0
1
-
0
P067
Serial CAN bus address
1
1
125
-
1
P068
Logic of the hydronic algorithms
0
0
7
-
0
P069
Network address
1
0
207
-
1
P070
Dependence of the hydronic algorithms (on slaves)
0
0
7
-
0
P071
Serial address of slave 1
0
0
207
-
0
P072
Serial address of slave 2
0
0
207
-
0
P073
Serial address of slave 3
0
0
207
-
0
P074
Serial address of slave 4
0
0
207
-
0
P075
Serial address of slave 5
0
0
207
-
0
P076
Serial address of slave 6
0
0
207
-
0
P077
Serial address of slave 7
0
0
207
-
0
P078
Serial address of slave 8
0
0
207
-
0