Venkon XL
Assembly, installation and operating instructions
38
7
Electrical connection
IMPORTANT NOTE!
Condensation formation in the cooling unit!
In the event of on-site valve control, the cooling valve must be closed when the fans are switched off.
7.1
Maximum electrical rating values
Venkon XL, KaControl model (*C1)
Size
Number of
fans
Nominal
voltage [V AC]
Mains fre-
quency [Hz]
Nominal
power [W]
Nom-
inal
current
[A]
Leakage
current
[mA]
Ri ana-
logue in-
put [KΩ]
IP class
Protection
class
1
1x single
230
50
172
1.5
1.29
20
IP21
I
2
1x tandem
230
50
244
2.0
1.29
20
IP21
I
3
1x single, 1x
tandem
230
50
423
3.3
2.58
20
IP21
I
4
2x tandem
230
50
498
3.9
2.58
20
IP21
I
Tab. 8: Maximum electrical rating values for Venkon XL, KaControl (*C1)
Venkon XL, electromechanical model (*00/*01)
Size
Number of
fans
Nominal
voltage [V AC]
Mains fre-
quency [Hz]
Nominal
power [W]
Nom-
inal
current
[A]
Leakage
current
[mA]
Ri ana-
logue in-
put [KΩ]
IP class
Protection
class
1
1x single
230
50
172
1.5
1.29
100
IP21
I
2
1x tandem
230
50
244
2.0
1.29
100
IP21
I
3
1x single, 1x
tandem
230
50
423
3.3
2.58
50
IP21
I
4
2x tandem
230
50
498
3.9
2.58
50
IP21
I
Tab. 9: Maximum electrical rating values for Venkon XL EC, electromechanical model (*00/*01)
7.2
Electromechanical control, Venkon XL
7.2.1 Connection (*00 or 00D), Venkon XL
Fig. 17: Remove junction box from the Velcro
strip
The junction box for electromechanical control can be electrically installed separ-
ately from the side panel of the basic unit by Velcro fitting. Simply remove the
plastic lid to open the junction box.