Venkon
Assembly, installation and operating instructions
43
7
Electrical connection
IMPORTANT NOTE!
Condensation formation in the cooling unit!
In the event of on-site valve control, the cooling valve must be closed when the fans are switched off.
7.1
Maximum electrical rating values
Venkon AC, electromechanical model (*00M / *01M)
Model
Number of fans
Nominal voltage
Mains fre-
quency
Nominal power
Nominal
current
Protection
rating
Protection
class
61
1x Single
230 V~
50 Hz
62 W
0.27 A
IP21
I
63
1x Tandem
230 V~
50 Hz
68 W
0.34 A
IP21
I
66
1x Single, 1x Tan-
dem
230 V~
50 Hz
129 W
0.59 A
IP21
I
67
2x Tandem
230 V~
50 Hz
145 W
0.71 A
IP21
I
Tab. 8: Maximum electrical rating values for Venkon AC
Venkon EC, electromechanical model (*00M / *01M)
Model
Number of
fans
Nominal
voltage
Mains fre-
quency
Nominal
power
Nom-
inal
current
Leakage
current
Ri ana-
logue in-
put
Protection
rating
Protection
class
61
1x Single
230 V AC
50 Hz
45 W
0.39 A
< 3.5
100 kΩ
IP21
I
63
1x Tandem
230 V AC
50 Hz
51 W
0.44 A
< 3.5
100 kΩ
IP21
I
66
1x Single, 1x
Tandem
230 V AC
50 Hz
95 W
0.84 A
< 3.5
50 kΩ
IP21
I
67
2x Tandem
230 V AC
50 Hz
102 W
0.89 A
< 3.5
50 kΩ
IP21
I
Tab. 9: Maximum electrical rating values for Venkon EC
Venkon EC, KaControl model (*C1M / *C1E)
Model
Number of
fans
Nominal
voltage
Mains fre-
quency
Nominal
power
Nom-
inal
current
Leakage
current
Ri ana-
logue in-
puts
Protection
rating
Protection
class
61
1x Single
230 V AC
50 Hz
48 W
0.42 A
< 3.5
20 kΩ
IP21
I
63
1x Tandem
230 V AC
50 Hz
54 W
0.47 A
< 3.5
20 kΩ
IP21
I
66
1x Single, 1x
Tandem
230 V AC
50 Hz
98 W
0.87 A
< 3.5
20 kΩ
IP21
I
67
2x Tandem
230 V AC
50 Hz
105 W
0.92 A
< 3.5
20 kΩ
IP21
I
Tab. 10: Maximum electrical rating values for Venkon EC, KaControl
Summary of Contents for Venkon 61
Page 2: ......
Page 86: ...Venkon Assembly installation and operating instructions 86 13 Certificates...
Page 90: ......
Page 91: ......