6.5.2 Sealing the pipework to the valve condensation tray
Proceed as follows when using the valve condensation tray to collect condensation from the valves:
Fig. 31: Insulation with wall-mounted units
Fit diffusion-tight insulation to the pipe from below through the opening of the
valve condensation tray to the top edge.
1
2
Fig. 32: Gluing rubber pipe collars with insula-
tion
1 Rubber pipe collar
2 Insulation
Press the rubber pipe collar
1
to the insulation
2
and the neck of the valve
condensation tray and glue in place.
Important:
There is a danger that condensation will escape if the insulation is
not leak-tight!
Fig. 33: Closing unused holes
Press plastic plugs (supplied) into unused holes in the valve condensation tray.
Fig. 34: Insulating with ceiling units
Fit diffusion-tight insulation as far as the area above the valve condensation
tray.