21
TOP unit heaters
1.53
Unit heaters (2-stage three-phase motor/1-stage AC single-phase motor/continuously variable EC single-phase motor)
Installation and operating instructions
Control signal
Speed of the TOP
0-1.0 V
Off
1.0-9.5 V
0-100 %
9.5-10.0 V
100 %
Table 3
Input resistance
Models 44,
45 and 46
Ri > 100 KOhm
BG 47
Ri > 50 KOhm
Table 4
Control via 0-100 KΩ potentiometer
When controlling using a 0-100 KΩ potentiometer (linear),
the jumpers for models 44, 45 and 46 and the DIP switches 1
and 2 for model 47 need to be wired/set at the potentiometer
(Models 44, 45 and 46, see Fig. 1, Model 47 see Fig. 4) on the
master unit (the TOP connected to the potentiometer). All
additional TOP (slave units) then need to have the jumper and/
or DIP switch position 0-5 V. (Models 44, 45 and 46 see Fig. 3,
Model 47 see Fig. 6).
Control via 0 - 10 VDC
When controlling using 0-10 VDC, the jumpers for models 44,
45 and 46 and the DIP switches 1 and 2 for model 47 need to
be wired/set at 0-10 V on all power modules (Models 44, 45 and
46, see Fig. 2, Model 47 see Fig. 5). The 0 - 10 V control signal
is interpreted with respect to its speed according to the table
(refer to table 3). Input resistance see Table 4.
Control via 0 - 5 VDC
When controlling using 0-5 VDC (e.g. on-site control), the
jumpers for models 44, 45 and 46 and the DIP switches 1 and
2 for model 47 need to be wired/set to 0-5 V on all power
modules (Models 44, 45 and 46, see Fig. 3, Model 47 see Fig. 6).
The speed does not behave linear to the control voltage with
this setting.
Input resistance see Table 4.
Models 44, 45 and 46: jumper setting Figs. 1 to 3
Model 47: DIP switch setting Figs. 4 to 6
Potentiometer,
left setting
Potentiometer
ON-OFF setting
0-10 V, middle setting
0-10 V,
OFF-OFF setting
0-5 V, right setting
0-5 V,
OFF-ON setting
0 - 10 V connection example
ΔΔ
0-10V
GND
Freigabe
Drehzahlsignal
Control signal
Fan speed
0-10 VDC
GND
AE
AE
DE
GND
Pot.
0-10V
0-5V
2 1 DIP
LED
GND