19
TOP unit heaters
1.53
Unit heaters (2-stage three-phase motor/1-stage AC single-phase motor/continuously variable EC single-phase motor)
Installation and operating instructions
Single-phase wiring diagrams
Wiring diagram 1 single-phase; factory wiring
Regelgerät
Regelgerät
Wiring diagram 2 single-phase; Reversal of fan
direction
Drehrichtungsumkehr durch Umverdrahtung von
zwei Motoranschlussadern:
Verbindung: U1-Z1 ==> U1-Z2
Verbindung: V1-Z2 ==> V1-Z1
Klemmenleiste
Motorklemmbrett
Klemmenleiste
Motorklemmbrett
Max. number of connectable TOP single-phase unit heaters per controller
TOP type series
Type
Imax.
44 _ _ 31
45 _ _ 31
46 _ _ 31
47 _ _ 31
7-stage single-phase controller
30771
4 A
5
3
2
1
7-stage single-phase controller
30772
7.5 A
10
5
4
3
Electronic continuously variable
Single-phase controller
30540
4.5 A
6
3
2
1
30543
Control unit
Control unit
Reversal of fan direction by switching the wires
of two motor connection wires:
Connection: U1-Z1 ==> U1-Z2
Connection: V1-Z2 ==> V1-Z1
Terminal board
Terminal board
Motor terminal board
Motor terminal board