Number of height-adjustment feet and raised floor mounting feet
9. Number of height-adjustment feet and
raised floor mounting feet
10. Maintenance
Information
Maintenance on
Ka
therm
NX floor ducts should only be carried out
by qualified personnel trained in compliance with the installation and
operating instructions as well as any regulations currently in force. Regular
maintenance and inspections are required in order to permanently
guarantee the function and performance of the
Ka
therm
NX.
Heat exchanger
l
Inspect the integral heat exchanger every six months for dirt and
possible damage. A visual inspection is sufficient here.
l
Carefully vacuum the heat exchanger if dirty.
Valves
l
Inspect the valves as well every 12 months and check the leak-tightness
(visual inspection)!
Duct length [mm]
Number of height-adjustment feet
Number of raised floor mounting feet
900
2
2
1100
2
3
1300
2
3
1500
2
3
1700
2
3
1900
2
4
2100
2
4
2300
2
4
2500
2
4
2700
2
4
2900
2
5
3100
2
5