ASSEMBLY AND INSTALLATION INSTRUCTIONS
1.48
Venkon
28
7. Installation, Venkon Wiring, Room Control Unit, Inlet
Air Temperature Sensor
7.1 Fan Convector
• The electrical cables are connected to the KaControl Venkon in
the electrical control box.
• The electrical control box is located behind one of the side
mullions and is always mounted on the opposite side to the valve
assemblies.
• To connect the electrical cables, open the electrical control box,
insert the cables and connect up as per the wiring diagram.
• Dismantle the side mullions as follows:
•
•
Open the operating flap
•
•
Loosen the screws on the inside of the side panel
•
•
Carefully raise the side casing approx. 20 mm until it comes
loose from the bracket.
•
•
Loosen the side mullions towards you.
•
•
Should a control unit (layout C2) be incorporated in the casing,
the cable should be isolated by loosening the reverse polarity
protected plug
•
•
Place the casing in a safe position
• Disconnect the KaControl Venkon prior to embarking on "any"
wiring work.
The bus lines should also only be connected to the KaControl
Venkon when the unit is fully disconnected.
Electrical
control box