Operating area

For proper functioning and a good temperature distribution, 
the stove shoul be positioned in a location where it is able 
to take in the air necessary for combustion of the pellet 
(about 40 m

3

/h must be available), as laid down in the 

standard governing the installation and in accordance with 
local national standards.
The volume of the room must not be less than 30 m

3

The air must come in through permanent openings made 
in walls (in proximity to the stove) which give onto the 
outside, with a minimum cross-section area of 100 cm

2

.  

These openings must be made in such a way that it is not 
possible for then to be obstructed in any way. Alternatively, 
the air can be taken from rooms adjacent to the one which 
needs ventilating, as long as they are provided with an air 
intake from the outside, and are not used as bedrooms or 
bathrooms, and provided there is no fire risk such as there 
is for example in garages, woodsheds, and storerooms, 
with particular reference to what is laid down in current 
standards. 

It is not permissible to install the ther-
mostove in bedrooms, bathrooms, or in a 
room where another heating appliance is 

installed (fireplace, stove etc.) which does not have 
its own independent air intake. 
Locating the thermostove in a room with an explo-
sive atmosphere is prohibited.
The floor of the room where the thermostove is 
to be installed must be strong enough to take its 
weight. If walls are flammable, maintain a minimum 
distance of 10 cm at the rear (A), of 40 cm at the 
side (B) and 100 cm at the front. 
If the room contains objects which are believed to 
be particularly delicate, such as drapes, sofas and 
other furniture, their distance from the thermostove 
should be considerably increased.

40 cm

Min.

100 cm

2

Connection to the external air intake

It is essential that at least as much air must be able to 
flow into the room where the thermostove is installed as 
is required for proper combustion in the appliance and for 
the ventilation of the room.
This can be effected by means of permanent openings in 
the walls of the room to be ventilated, which give onto the 

outside, or by single or collective ventilation ducts.
For this purpose, on the external wall near the thermostove, 
a hole must be made with a minimum free cross-section 
of 100 cm

2

. (equivalent to a round hole of 12 cm diameter 

or a square hole 10x10 cm) protected by a grille on the 
inside and the outside.
The air intake must also: communicate directly with the 
room where the thermostove is installed be protected by 
a grille, metal mesh or suitable guard, as long as this does 
not reduce the area below the minimum.
Be positioned in such a way as to be impossible to 
obstruct.

In the presence of wood floors, install a 
floor protection surface in compliance 
with the rules in force in the country

Summary of Contents for 24B

Page 1: ...USER MANUAL Ilaria Nadia 24B 24BDD Boiler Stoves Instructions for the correct use and maintenance of your Kalor wood pellet boiler stove Distribution and warranty in Ireland by...

Page 2: ...so offer a nationwide network of Authorised Technicians who are specially trained on Kalor wood pellet stoves This ensures that your stove can be correctly installed commissioned maintained and repair...

Page 3: ...s in operation several parts of the stove door handle sides can reach high temperatures Therefore pay attention and use the proper precautions above all in the presence of children elderly or disabled...

Page 4: ...for accidents deriving from the partial or total lack of observance of the instruc tions contained herein We decline every responsibility derived from improper use of the stove from incorrect use by...

Page 5: ...hlike must be kept a suitable distance from the stove Risk of fire Carefully explain that the thermostove is made from ma terial subjected to high temperatures for the elderly the disabled and in part...

Page 6: ...s prohibited The floor of the room where the thermostove is to be installed must be strong enough to take its weight If walls are flammable maintain a minimum distance of 10 cm at the rear A of 40 cm...

Page 7: ...nless steel pipe must not be used At the bottom of the flue pipe provide an inspection cap to allow periodic checking and cleaning which must be done annually Make a gas tight connection to the flue p...

Page 8: ...be a wind proof type and must be above the ridge Eventual structures or other obstacles that are higher than the chimney cap must not be too close to the chimney cap itself Fig 5 Characteristics of c...

Page 9: ...LERANZE GENERALI DI LAVORAZIONE DIMENSIONI LINEARI 0 15 0 05 3 2 0 1 DIMENSIONI ANGOLARI PRECISIONE 12 GRADO DI FINO A 0 15 0 1 6 0 3 0 25 120 0 2 0 15 60 6 60 0 3 0 2 0 5 4000 0 8 0 6 1000 400 0 5 0...

Page 10: ...54 Pellet consumption min max Kg h 0 84 3 79 Heated surface mc 430 Flue gas flow rate min max g s 3 02 11 04 Draft min max Pa 3 8 Flue gas temperature min max C 51 1 103 Boiler water litri 31 Maximum...

Page 11: ...ly connected to the system and to allow slighht movement Diagram connection kit without hot water thermostove Plumbing system connection There are 2 different types of systems Closed vessel system Ope...

Page 12: ...3 bar the water used for filling the heating system must be decontaminated and without air When all the hydraulic connections are done proceed to test the pressure of the seals through the filling of...

Page 13: ...sed If you have very extensive system with a large amount of water or which require frequent refilling it is recommended the installation of water softening system It should be noted that the encrusta...

Page 14: ...termostato ext encoder ventilatore fumi encoder ventilatore fumi m 1 0 07 04 2017 P B C SCHEDA Q055 SCHEDA L023 LATO RISC Cn2 P2 P4 F P3 3VIE LATO SANIT N N TURBOLATORE OPZIONALE F PULITORE COMPATTAT...

Page 15: ...IZED TECHNICIAN How to select the type of Stand by OPERATION BY A SPECIALIZED TECHNICIAN Press the SET button press button to go to menu 09 Press the SET button again Enter the access key and confirm...

Page 16: ...adjust it with the e Reaction from the stand by state is when a heat increase is required to return to a chosen stand by condition when it is set to ON or when there is a health risk II I I Valve mot...

Page 17: ...AM 25 STAND BY IF PROBE H2O SET H2O a HEATING SANITARY HEALTH CALL ON 02 H2O WINTER ON IF H2O PARAM 25 MODULE IF PROBE H2O 80 C HEATING SANITARY SANITARIO NON CHIAMA OFF 03 TERM ES WINTER ON IF H2O PA...

Page 18: ...adjust it with the and keys The rinsing from the stand by state occurs automatically when a heat increase is required to return to satisfy the chosen stand by condition when this is set to ON or when...

Page 19: ...25 STAND BY IF PROBE H2O SET H2O a HEATING SANITARY HEALTH CALL ON 02 H2O WINTER ON IF H2O PARAM 25 MODULE IF PROBE H2O 80 C HEATING SANITARY SANITARIO NON CHIAMA OFF 03 TERM ES WINTER ON IF H2O PARA...

Page 20: ...adjust it with the and keys The rinsing from the stand by state occurs automatically when a heat increase is required to return to satisfy the chosen stand by condition when this is set to ON or when...

Reviews: