2.4. Kalfire W53/50R model in combination with
flammable materials (e.g. a wooden wall)
during installation, pay attention to the distance to the flammable
building materials:
figure 3: Cross-section of a Kalfire w room divider in combination with
flammable materials
flammable materials must be protected by insulation material
that is at least 10-cm thick. The distance from the back of the
fireplace to the insulation material must be a minimum of 10 cm.
DANGER! The floor on which you place the Kalfire w53/50r
model must consist of non-flammable materials. The floor
in front of the door opening must be protected to a distance of
at least 50 cm in front of the appliance (sides with a glass door).
DANGER! if the w53/50r model is placed directly (without
an air gap) against a wall made of flammable material and
10 cm of insulation, the fireplace may only be used for a
maximum of 16 hours.
2.5. Kalfire W65/38C model in combination with
flammable materials (e.g. a wooden wall)
during installation, pay attention to the distance to the flammable
building materials:
figure 4: Cross-section of a Kalfire w65/38C model in combination with
flammable materials
2.3. Kalfire front model in combination with flammable
materials (e.g. a wooden wall)
during installation, pay attention to the distance to the flammable
building materials:
flammable materials must be protected and/or insulated by
insulation material. The minimal thickness (a) of the material
depends on the type of insulation material and the fireplace in
which it is used. The minimal thickness can be consulted in Table 1.
The distance from the back or the side of the fireplace (if has been
built into an alcove) to the insulation material must be a minimum
of 10 cm.
DANGER! ensure that curtains, furniture and/or other
flammable materials are at a minimum distance of 150 cm
from the fireplace.
WARNING ensure that windows are at least 100 cm away
from the fireplace.
DANGER! The floor on which the fireplace is placed must
consist of non-flammable materials. in front of the door to
the fireplace, the (flammable) base should be protected
(30 cm on both sides and 50 cm in the front of the fireplace).
100
100
50
50
figure 2: Cross-section of a Kalfire w front model in combination
with a flammable wall
A
100
Insulation
Flammable material
10