Troubleshooting
LFIS-B-1211
90
Electrical Control System
2.4 Solving steps for typical malfunction
2.4.1 For the indoor unit
2.4.1.1 Open or short circuit of temperature sensor
Check the connections
between temperature
sensor and PCB. Are
the connections good?
Correct the connections.
No
Yes
Yes
Replace indoor or outdoor PCB.
Replace the sensor
Check the resistance value
of the sensor via Appendix 1
Is it normal?
No