1.3.2.4 Evaporator low temperature T2 protection.
When T2<2
℃
and lasts for 3 minutes, the indoor has no capacity demand and resume till T2
≥
7
℃
.
1.3.2.5 Condenser high temperature T3 protection
When T3≥65
℃
for 3 seconds, the compressor will shut off. When T3
<
52,the compressor will restart.
1.3.3 Heating Mode
1.3.2.1 Outdoor PMW open angle control
The unit is working in heating mode with the EXV open 300P for 3 minutes, then adjusting PMW open angle
according to the temperature of compressor discharge every 2 minutes.
1.3.3.2 Outdoor fan running rules:
T4
E
DC_FAN_SSLOW_SPD_ADD
D
DC_FAN_SLOW_SPD_ADD
C
DC_FAN_MIN_SPD_ADD
B
DC_FAN_MID_SPD_ADD
A
DC_FAN_HI_SPD_ADD
21
℃
19
℃
18
℃
16
℃
15
℃
13
℃
12
℃
10
℃
1.3.3.3 Indoor fan running rules:
When the compressor is on, the indoor fan can be set to high/(med)/low/auto. And the anti-cold wind
function has the priority.
Auto fan action:
Summary of Contents for SUPER DC INVERTER SERIES
Page 1: ...Contents i New Energy Requirement SUPER DC INVERTER SERIES Service Manual 2012 LFIS B 1211 ...
Page 2: ...ii General Information ...
Page 4: ......
Page 17: ...LFIS B 1211 Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Page 23: ...LFIS B 1211 Field Wiring Indoor Units 19 9 Field Wiring ...
Page 36: ...Duct Type LFIS B 1211 32 Indoor Units 10 Field Wiring ...
Page 40: ...Duct Type LFIS B 1211 36 Indoor Units 3 Service Space ...
Page 44: ...Field Wiring LFIS B 1211 40 Part 3 9 Field Wiring ...
Page 50: ...Wiring Diagrams LFIS B 1211 46 Part 3 KOU 36HFN1 RRC4 ...
Page 100: ...Troubleshooting LFIS B 1211 96 Electrical Control System 2 4 2 3 Up down panel is not closed ...