Troubleshooting
LFIS-B-1211
110
Electrical Control System
2.4.4.14. P4 malfunction
When
compressor discharge temperature is higher than 115°C, the unit will stop, and unit runs again when
compressor discharge temperature is lower than 90°C.
P4 display
Temperature protection of
compressor discharge
Check whether the
compressor discharge temp.
is more than 115°C ?
Check whether the wiring
connection is right between
compressor discharge temp.
sensor and PCB according
to wiring diagrams?
Method: Check whether the
resistance of compressor
discharge temp. sensor is
right refer to the
Appendix
2
No
Yes
Yes
Trouble is solved
No
Judge: The
discharge temp.
sensor is broken
Check whether the
refrigerant is leak
Correct the wiring connection
Stop leaking and add refrigerant
Replace the compressor discharge temp. sensor
No
Yes
Replace outdoor main board
Yes
Summary of Contents for SUPER DC INVERTER SERIES
Page 1: ...Contents i New Energy Requirement SUPER DC INVERTER SERIES Service Manual 2012 LFIS B 1211 ...
Page 2: ...ii General Information ...
Page 4: ......
Page 17: ...LFIS B 1211 Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m ...
Page 23: ...LFIS B 1211 Field Wiring Indoor Units 19 9 Field Wiring ...
Page 36: ...Duct Type LFIS B 1211 32 Indoor Units 10 Field Wiring ...
Page 40: ...Duct Type LFIS B 1211 36 Indoor Units 3 Service Space ...
Page 44: ...Field Wiring LFIS B 1211 40 Part 3 9 Field Wiring ...
Page 50: ...Wiring Diagrams LFIS B 1211 46 Part 3 KOU 36HFN1 RRC4 ...
Page 100: ...Troubleshooting LFIS B 1211 96 Electrical Control System 2 4 2 3 Up down panel is not closed ...