88
English
External
air t
1
Supply
air t
2
Exhaust
air t
4
UNITS
EQUIPPED
WITH
ANTIFREEZE
SYSTEM
Antifreeze electric resistance switch on
Setpoint t4=4°C
<-3°C
–
<4°C
–
–
<1°C
Electric resistance shutdown
>0°C
–
–
Activation of preheating water coil valve
or ON/OFF resistance
<-3°C
–
<3°C
–
–
<1°C
Valve closure or ON/OFF resistance shutdown
–
–
>6°C
Speed reduction of both fans
with proportional law with decreasing t4.
Electric resistance malfunctioning alarm
<-3°C
–
<3.5°C
Unit switch off with “Frost” alarm
<-3°C
–
<1°C
<-20°C
–
–
UNITS WITHOUT
ANTIFREEZE
SYSTEM
Defrost cycles:
the input fan is brought to minimum speed for 10min an hour
<-5°C
–
–
Unit switch off with “Frost” alarm
<-10°C
–
–
ALL
UNITS
Input air low temperature alarm
–
<10°C
–
Unit switch off with “Frost” alarm
–
<5°C
–
When the Frost alarm is triggered, the unit switches OFF and restarts automatically when the critical climatic condition disappears.
The Frost alert remains until the next time the unit is switched off and back on.
Antifreeze protective circuit chart
For units not equipped with integrated electric
resistance, a duct modulating electric resistance is
available as a preheating accessory.
• Without Electric Resistance
In case the unit is without an electric antifreeze resist-
ance, the unit has preventive operation logic which,
below -5°C, automatically sets running of the intake
fan at minimum for 10 minutes every hour.
Also, in case the temperature falls below -10° C, the
unit stops automatically and an alert appears on the
display of the controller: “
FROST
”
.
When the Frost alarm is triggered, the unit switches
OFF and restarts automatically when the critical
climatic condition disappears. The Frost alert remains
until the next time the unit is switched off and back on.
Summary of Contents for KVX-270 RHQ
Page 2: ......
Page 3: ...INSTRUKCJAOBS UGI OWNER SMANUAL BEDIENUNGSANLEITUNG 5 55 123 PL EN DE...
Page 4: ......
Page 23: ...23 Polski Instalacja sterownika na cianie 1 2 3 4 1 2 3 4 60 9 10 8 10 9 57 56...
Page 53: ......
Page 54: ......
Page 71: ...71 English Installing controller on the wall 1 2 3 4 1 2 3 4 60 9 10 8 10 9 57 56...
Page 101: ...101 English...
Page 102: ......
Page 117: ...16 Deutsch 1 2 3 4 Installation der Wandbedieneinheit 1 2 3 4 60 9 10 8 10 9 57 56 Deutsch 117...
Page 146: ......
Page 147: ......
Page 148: ...kaisai com...