26
2. The interval time for mode switching:
When the mode needs to be switched, the heat pump must run in the current mode for at least 10
minutes before switching to another mode.
Mode information on the display
12.4. Parameters
12.4.1. Parameter list
Code
Parameter
Setting range
SG01
SG Ready Application
0- Disabled
1- One potential-free contact
2- Two potential-free contacts
SG02
Block Time of Mode 1
0-120 min
SG03
Limited Power in Solar
Low Mode 2
0-99,9 kW
SG04
Limited Power in Solar
Medium Mode 3
0-99,9 kW
SG05
Additional Hot Water
Temp. in Mode 4
0-25°C
SG06
Additional Heating Water
Temp. in Mode 4
0-25°C
SG07
Additional Cooling Water
Temp. in Mode 4
0-25°C
SG08
Turn On the Electric Heater
Immediately in Mode 4
0-No/1-Yes