INITIAL SETUP:
The M-522 is a programmable unit requiring initial setup in order to properly operate the devices
intended, and to customize the function of the unit dependent on various connection
requirements to other controllers that are to operate in conjunction with the M-522 such as
external General Alarm Systems.
Setting SW1 Switches
On the internal circuit board of the M-522 there is a switch assembly labeled SW1. Settings on
this switch assembly determine permanent functionality of the unit not programmable from the
keypad. Settings and functionality are as follows:
SW1 Functionality:
SW1
Tab 1
CAN Address (LSB)
Tab 2
CAN Address (MSB)
Tab 3
CAN Communication
(Off = Disable On = Enable)
Tab 4
Ship Size (Off <100m On >100m)
Tab 5
GEA Function (MSB)
Tab 6
GEA Function (LSB)