cLr :A
ccumulated energies can be erased in this section.
The parameters which indicated by the LEDs at the top of the device, will be
erased.
▲
▼
SET
▲
▼
▲
▼
SET
▲
▼
▲
▼
SET
▲
▲
▼
Exit Menu
CLR
RES ALL PAR
QUIT
CLR ENERGY
YES
rES ALL PAr :
A
ll parameters are erased and factory settings are restored
increase
decrease
increase
decrease
Operating Voltage (Un)
: (Phase-Neutral ) 230Vac
Operating Range
: (0,8-1,1) x Un
Operating Frequency
: 50/60 Hz
Supply Power Consumption : < 6VA
Power Consumption
of Measurement Inputs:
: < 1VA
Vin
: 1 – 300 Vac (L-N)
: 2 – 600 Vac (L-L)
Iin
: (as the secondary current of
the current transformer)
0,01 - 6 Amp AC
Measurement Class
: CAT III
Voltage Transformer Ratio: : 1 ..... 4000
Current Transformer Ratio : 1 ..... 5000 (25000/5A)
Connection Type
: 3P&4W , 3P&3W , ARON
Demand Time
: 1 – 600 min
Display range
: 1,0V - 400,0 kV
: 0,001A ........ 25000 A
: 0 – 999,9 M (W,VAR,VA)
: 0 – 999,9 k (W,VAR,VA)
: 0 – 999.999.999,999 (GWh,GVARh,GVAh)
accuracy
Active Power
: 1 class
Reactive Power
: 2 class
Apparent Power
: 1 class
Pulse Outputs
(2 pcs)
Operating Voltage
: 5 – 24Vdc max. 30Vdc
Operating Current
: max 50 mA
Min. Switching Time
: 100 ms
Technical Specifications
Device Protection Class
: IP 20
Terminal protection class
: IP 00
Ambient temperature
: - 5 °C .... + 50 °C
Installation Type
: DIN rail
Dimensions
: 105x90x59 mm
NOTE: Operating Voltage (Un): ask price and delivery time for 85-256Vac/dc
N
1
Σ
N
P
i
i=0
P
=
N
1
Σ
N
Q
i
i=0
Q
=
S =
P
2
Q
2
+
PF =
P
S
Active Power
Reactive Power
Apparent Power
Power Factor
Formulas
Current Transformer(Primary) Value
:
5
/ 5 A
Voltage Transformer Ratio
:
1
Pulse Type for 1.Pulse Output
: OFF
Pulse Value for 1. Pulse Output
(Pd)
: 1 KWh
Pulse Duration for 1.Pulse Output
(Pt)
: 100 ms
Pulse OFF Time for 1.Pulse output
(Pp) : 200 ms
Pulse Type for 2.Pulse Output
: OFF
Pulse Value for 2. Pulse Output
(Pd)
: 1 KVARh
Pulse Duration for 2.Pulse Output
(Pt)
: 100 ms
Pulse OFF Time for 2.Pulse output
(Pp) : 200 ms
Factory Settings
1.
P
ul
se
o
up
ut
t
2.
P
ul
se
o
ut
pu
t
Note :
When factory settings
are restored, energies are set to zero.