Parameters

ut    rate

ut    rate

ut    rate

PULS    OUT

0001

0001.0

PULSOUT1

PULSOUT2

Ct :Current Transformer Ratio 

( 1........5000 ) Current transformer ratio value

 is entered.Example: For 500 / 5A is entered 100. (500/5A=100)

Ut :Voltage Transformer Ratio   

( 1........4000 )Voltage transformer ratio value is

 entered.Example: For 34500 /100V is entered 345.  (34500/100V=345)

Puls out:

The device has two digital pulse output. Menus and functions are the 

same for the two outputs.Outputs can be set differently according to the type of 
 the desired energy

cLr : 

delete 

rES  ALL  PAr : 

A

ll parameters are erased and factory settings are restored

quit :

 quit from parameter menu

max.30Vdc

C

O1

O2

t (ms)

t (ms)

Pd

Pt

Pt

Pt

Pd

Pd

Energy

5 – 24V
Max 30V

Pp

Pp

1. puls out

NOTE: 

If one of the three parameters P,Q,S is activated,

the other two parameter will not appear in the setting menu.
You can access to the other parameters menus only if they
are all deactivated.

max.30Vdc

C

O1

O2

+-

 usage with relay

Connection to another device as insulated

+-

SET

PULSOUT1   p

PULSOUT1   Q

PULSOUT1   s

SET

pulstype

pulsdeal

Puls per

SET

pulstıme

quıt

SET

SET

SET

pulstype

pulsdeal

Puls per

pulstıme

pulstype

pulsdeal

Puls per

pulstıme

pulstype

pulsdeal

Puls per

pulstıme

pulstype

pulsdeal

Puls per

pulstıme

off

0.1

50

50

SET

Pulse Type (PULS tyPE) :

For Reactive Energy, it can be 
selected as import(ind)-import(kap)
-export(ind) -export(kap)-OFF 

Pp

 (PULS PEr):

 Pulse delay time

It can be selected between 50ms – 900 ms

Pt (PULS tınE)

 :

 

Pulse Time  It can be selected between
50ms – 900 ms

Pd (PULS dEAL) :

 1

The amount of energy equivalent to Pulse.
It can be selected between 0,1kWh – 10MWh  

2. puls out

Active energy settings

Reactive 
energy
settings

Apparent
energy
settings

 

increase

decrease

increase

decrease

 SET button is pressed for 3 seconds, the parameter menu can be accessed. First parameter is current transformer ratio. After pressing 
the SET key, value is increased or decreased by using the arrow keys. By pressing the SET button, the new value will be saved.

Pulse Type (PULS tyPE) : 

For Active Energy, it can be 
selected as

 import-export-OFF

when amount of each energy (Pd) occurs , 
a pulse is generated from output, during time of (Pt). 
And then, output stays as 0V ,during time of (Pp)