SET
Ct rate
SET button is pressed for 3 seconds
SET
increase
decrease
▲
▼
SET
▲
▼
▲
▼
▲
▼
SET
▲
▼
Parameters
ut rate
ut rate
ut rate
PULS OUT
0001
0001.0
PULSOUT1
▼
▼
▲
▲
PULSOUT2
Ct :Current Transformer Ratio
( 1........5000 ) Current transformer ratio value
is entered.Example: For 500 / 5A is entered 100. (500/5A=100)
Ut :Voltage Transformer Ratio
( 1........4000 )Voltage transformer ratio value is
entered.Example: For 34500 /100V is entered 345. (34500/100V=345)
Puls out:
The device has two digital pulse output. Menus and functions are the
same for the two outputs.Outputs can be set differently according to the type of
the desired energy
cLr :
delete
rES ALL PAr :
A
ll parameters are erased and factory settings are restored
quit :
quit from parameter menu
max.30Vdc
C
O1
O2
t (ms)
t (ms)
Pd
Pt
Pt
Pt
Pd
Pd
Energy
5 – 24V
Max 30V
Pp
Pp
1. puls out
NOTE:
If one of the three parameters P,Q,S is activated,
the other two parameter will not appear in the setting menu.
You can access to the other parameters menus only if they
are all deactivated.
max.30Vdc
C
O1
O2
+-
usage with relay
Connection to another device as insulated
+-
SET
PULSOUT1 p
PULSOUT1 Q
PULSOUT1 s
▼
▼
▲
▲
▲
▲
▼
▼
▲
▲
▲
▲
SET
pulstype
pulsdeal
Puls per
▼
▼
▲
▲
▼
▼
▲
▲
SET
pulstıme
quıt
▲
▲
▼
▼
▲
▲
▲
▲
▲
▲
▼
▼
▲
▲
▲
▲
▲
▲
▲
▲
SET
SET
SET
pulstype
pulsdeal
Puls per
▼
▼
▲
▲
▼
▼
pulstıme
▲
▲
▼
▼
▲
▲
▲
▲
▼
▼
▲
▲
▲
▲
pulstype
pulsdeal
Puls per
▼
▼
▲
▲
▼
▼
pulstıme
▲
▲
▼
▼
▲
▲
▲
▲
▼
▼
▲
▲
▲
▲
pulstype
pulsdeal
Puls per
▼
▼
▲
▲
▼
▼
pulstıme
▲
▲
▼
▼
▲
▲
▲
▲
▼
▼
▲
▲
▲
▲
pulstype
pulsdeal
Puls per
pulstıme
off
0.1
50
50
SET
▼
▼
▲
▲
▼
▼
▲
▲
▼
▼
▲
▲
▼
▼
▲
▲
Pulse Type (PULS tyPE) :
For Reactive Energy, it can be
selected as import(ind)-import(kap)
-export(ind) -export(kap)-OFF
Pp
(PULS PEr):
Pulse delay time
It can be selected between 50ms – 900 ms
Pt (PULS tınE)
:
Pulse Time It can be selected between
50ms – 900 ms
Pd (PULS dEAL) :
1
The amount of energy equivalent to Pulse.
It can be selected between 0,1kWh – 10MWh
2. puls out
Active energy settings
Reactive
energy
settings
Apparent
energy
settings
increase
decrease
increase
decrease
SET button is pressed for 3 seconds, the parameter menu can be accessed. First parameter is current transformer ratio. After pressing
the SET key, value is increased or decreased by using the arrow keys. By pressing the SET button, the new value will be saved.
Pulse Type (PULS tyPE) :
For Active Energy, it can be
selected as
import-export-OFF
when amount of each energy (Pd) occurs ,
a pulse is generated from output, during time of (Pt).
And then, output stays as 0V ,during time of (Pp)