20
Kaden Installer's Manual
Ducted Gas Heaters
4.3 INSTALLATION
4.3.1 Area to Cut Out in Wall
When installing the heater at ground level,
create one rectangular hole to suit the total
POP width and height, all the way to ground
level, (refer to Diagram 14)
Ground level
Level concrete base
Base Box
Wall cut-out areas
NOTE
Refer to the Base Box for required
wall cut out dimensions.
Diagram 14
4.3.2 Installation of Flashing
Flashing
MUST BE
fitted to ensure the ductwork is adequately weather protected.
Step 1.
Fit side flashing using existing screws on
cabinet sides.
Step 2.
Slide top flashing under flashing rail on
base box
Silcone
Step 3.
Sit top flashing on top of side flashing
edges. Once in place silicone along the
upstanding face of top flashing.
Step 4.
Push the heater up against the wall and
secure side flashing to the wall.