28
| Kaden Installation Manual
4. Remove two fixing screws, then remove front panel.
5. Use a hammer and a flat blade screwdriver to knock out
the two metal electrical knock outs.
6. Connect the u-lugs to the terminals. Match the correct wire
with the correct label on the terminal block. Firmly screw
the u-lug of each wire to its corresponding terminal.
7. Clamp down the cable with the wire clamp.
8. The power cables and interconnect power cables will enter
the unit separately through the two knock out holes on the
bottom right side panel and be fastened with a lock ring
adaptor or rubber grommet. Wires should be bound with
cable ties and fixed to the internal side of the right chassis
panel as shown in the figure below.
Magnetic ring
(if supplied and packed with the accessories)
Signal wiring between outdoor and
indoor units
Use 2-core shielded data cable to connections S1, S2 and
shield on both outdoor and indoor units. Do not run this cable
next to high amperage loads. See wiring diagram adhered to
the electrical enclosure cover panel.
Indoor unit wiring
1. Prepare the cable for connection
a. Using wire strippers, strip the rubber jacket from both
ends of the signal cable to reveal about 15cm of
the wire.
b. Strip the insulation from the ends of the wires.
c. Using a wire crimper, crimp the u-lugs to the ends
of the wires.
2 screws
Pass the belt through the
hole of the magnetic ring
to fix it on the cable