3 Place the right housing cover on the device housing.
4 Fix the housing cover to the housing from the inside using the 2 enclosed M4x10 screws.
7
Installation
7.1
General information
DANGER
Lethal voltages are still present in the connections and cables of the device even after the device has
been switched off and disconnected!
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched.
›
The device must be mounted in a fixed position before being connected electrically.
›
Comply with all safety regulations and current technical connection specifications of the responsible
power supply company.
›
The device is only permitted to be opened or serviced by a qualified electrician.
›
Switch off the grid voltage by turning off the external circuit breakers.
›
Check that all AC and DC cables are completely free of current using a clip-on ammeter.
›
Do not touch the cables and/or terminals/busbars when switching the device on and off.
›
Keep the device closed when in operation.
7.2
Opening the device
↻
Mount the device to the wall.
↻
Wipe off any moisture on the housing door frame to nullify any potential liability
this could cause.
1 Open the housing door by unlocking the upper and lower lock with the double-
bit key provided.
2 Open the housing door carefully.
»
Proceed with the installation of the device.
Open
Close
Close
Open
Fig. 11:
Open the door lock
7.3
Surveying the connection area
The connection point for the AC supply is situated inside the housing. The DC input source is also connected inside the
housing.
Powador 39.0TL3 , Powador 39.0 TL3 M1 , Powador 40.0 TL3 , Powador 48.0 TL3 Park , Powador 60.0 TL3 ,
Powador 72.0 TL3 Park