AC-side
Length of insulation to be stripped off
abhängig von dem eingesetzen Klemmen-Bautyp
Tightening torque
2,5 - 4 Nm / 4 - 4,5 Nm (39.0-48.0TL3) Nm
Connection type
Schraubklemme
Ground conductor connection
M8
Fuse protection for installation provided by customer
100 A bei 35mm² / 63 A bei 16 mm²
Fitting for AC connection
M50
Cable diameter for cable fitting
11 - 17 (M25) 5 - 9,5 (M16) mm
Torque for cable fitting
5 (M25) 2,5 (M16) Nm
Interfaces
Interface screw connections
Ethernet: M25, Standard RS485: M16, max. 1,5 mm
Cable diameter for cable fitting
11 - 17 (M25) 5 - 9,5 (M16) mm
RS485 connection type
Steckverbinder
RS485 terminal cable cross-section
0,25 - 1,5 mm²
Ethernet connection type
RJ45
Torque for cable fitting
5 (M25) 2,5 (M16) Nm
7.5
Connecting the device to the power grid
7.5.1
Prepare the grid connection
TN-S system
↻
Connection cable with 5 strands is provided on the device.
↻
Nominal grid voltage matches the VAC nom name plate details.
1 Unfasten the cable fitting for the AC connection [ W_46].
2 Remove the outer cladding of the AC cables.
3 Insert the AC cables through the cable fitting into the connection area.
4 Strip the AC lines [approx. 25 mm].
»
Make the grid connection.
TN-S system
↻
Connection cable with 5 strands is provided on the device.
↻
Nominal grid voltage matches the VAC nom name plate details.
1 Unfasten the cable fitting for the AC connection [ W_46].
2 Remove the outer cladding of the AC cables.
3 Insert the AC cables through the cable fitting into the connection area.
4 Strip the AC lines [approx. 25 mm].
»
Make the grid connection.
1
2
Fig. 21:
Terminals
1
AC side
2
DC-side
Powador 39.0TL3 , Powador 39.0 TL3 M1 , Powador 40.0 TL3 , Powador 48.0 TL3 Park , Powador 60.0 TL3 ,
Powador 72.0 TL3 Park
Page 19