Flue systems
6 720 645 817
(2010/09)
85
Flue accessories
Flue lengths
Description
Ø 125 mm
(
Æ
page 92 ff.)
Ø 160 mm
(
Æ
page 97 ff.)
Ø 200 mm
(
Æ
page 103 ff.)
Ø 250 mm
(
Æ
page 109 ff.)
Boiler flue connection, 87° bend
AZB 1350
AZB 1350
AZB 1351
AZB 1351
AZB 1351
Boiler flue connection, straight
AZB 1352
AZB 1352
AZB 1353
AZB 1353
AZB 1353
1
Facade pack
AZB 1331
AZB 1332
AZB 1333
AZB 1334
2
Terminal piece
AZB 1358
AZB 1359
AZB 1360
AZB 1335
Terminal pipe
AZB 1049
AZB 1050
AZB 1051
–
Clamping strap
AZB 1056
AZB 1057
AZB 1058
–
Roof outlet, facade
AZB 1027
AZB 1042
AZB 1043
AZB 1044
Universal roof tile
AZB 923
AZB 925
AZB 1320
AZB 1321
–
–
Roof tile, special
–
–
AZB 1341
AZB 1342
Flat roof flange
AZ 136
AZB 1322
AZB 1344
AZB 1345
3
Wall mounting bracket
AZB 1045
AZB 1046
AZB 1047
AZB 1048
4
Extension pipe 0.5 m facade
Extension pipe 1 m facade
AZB 1001
AZB 1005
AZB 1002
AZB 1006
AZB 1003
AZB 1007
AZB 1004
AZB 1008
45° bend with inspection aperture,
facade
AZB 1015
AZB 1016
AZB 1017
AZB 1018
5
Inspection aperture, facade
AZB 1023
AZB 1024
AZB 1025
AZB 1026
6
Wall duct
AZB 1336
AZB 1337
AZB 1338
AZB 1339
7
Extension pipe 0.5 m
Extension pipe 1 m
AZB 977
AZB 718/1
AZB 978
AZB 982
AZB 979
AZB 983
AZB 980
AZB 984
8
Inspection aperture
AZB 720/1
AZB 994
AZB 995
AZB 996
87° bend (90°)
AZB 934
AZB 974
AZB 975
AZB 976
45° bend
AZB 940
AZB 970
AZB 971
AZB 972
30° bend
AZB 724/1
AZB 966
AZB 967
AZB 968
15° bend
AZB 719/1
AZB 964
–
–
87° bend with inspection aperture
AZB 997
AZB 998
AZB 999
AZB 1000
Reduction adaptor
AZB 1346
AZB 1309
AZB 1347
–
Enlargement adaptor
–
–
AZB 961
AZB 962
Tab. 52
Maximum permissible effective height of flue L in m
1)
1) Basis for calculation: Overall length of the connection piece
≤
2.5 m; effective height of connection line
≤
1.5 m; 2 x 87° bends
Suprapur
DN 125
DN 160
DN 200
DN 250
KBR 120-3 A
22
50
–
–
KBR 160-3 A
–
50
–
–
KBR 200-3 A
–
35
50
–
KBR 240-3 A
–
15
50
–
KBR 280-3 A
–
–
50
–
MKB 240-3 A
–
–
14
–
MKB 320-3 A
–
–
20
–
MKB 400-3 A
–
–
–
20
MKB 480-3 A
–
–
–
25
MKB 560-3 A
–
–
–
27
Tab. 53 Internal diameter and effective height of flues according to the requirements of DIN-EN 13381-1
Bend
Equivalent pipe length
90°
2 m
15° - 45°
1 m
Tab. 54 Equivalent pipe lengths of bends