Figure 24: Power Cord and Retainer Clip
ON
FAULTPWR OKINP2
INP1
1 2
g050569
ON
FAULTPWR OKINP2
INP1
1 2
1
2
2
—
1
—
Enable switch for INP2 appears as INP1 in output.
Enable switch for INP1 appears as INP0 in output.
WARNING:
Ensure that the power cords do not block access to router components or drape
where people can trip on them.
17. If the AC power source outlets have a power switch, set them to the on (|) position.
18. Move the enable switches for input 1 and input 2 to the ON position.
19. Verify that the INP1 and INP2 LEDs on the power supply faceplate are lit and are on steadily.
20. Press the power switch to the on (|) position.
Install AC/HVAC/HVDC Power Supplies (JNP10K-PWR-AC2)
The JNP10K-PWR-AC2 power supply is a high-capacity, high-line model that is designed to support either AC or DC
systems in either a low power or high power mode. The power supply takes AC input and provides DC output of 12.3
VDC, 5000 W with a single feed and 5500 W with a dual feed. For AC systems, the operating input voltage is 180 to 305
VAC and for DC systems, the operating input voltage is 190 to 410 VDC.
CAUTION:
Use the same type of power supply in all slots. Do not mix power supply models in the
same chassis.
25