background image

Presence detector

Presence detector Standard
Art. no.: 3361 WW
Presence detector Standard
Art. no.: 3361 AL
Presende detector Universal
Art. no.: 3361-1 WW
Presende detector Universal
Art. no.: 3361-1 AL

Operating instructions

1

Safety instructions

Electrical devices may only be mounted and connected by electrically skilled persons.

Serious injuries, fire or property damage possible. Please read and follow manual fully.

Do not press on the sensor window. Device can be damaged.

The device is not suitable for use as a burglar alarm or other alarm.

These instructions are an integral part of the product, and must remain with the end customer.

2

Battery safety instructions

This device or its accessories are supplied with batteries in the form of button cells.

DANGER! Batteries can be swallowed. This can lead directly to death by suffocation. Danger-
ous substances may cause severe internal burns leading to death within 2 hours.
Keep new and used batteries away from children.
Do not use devices if the battery compartment does not close securely and keep away from
children.
If you suspect that a battery has been swallowed or is in any orifice of the body, seek immediate
medical attention.

WARNING! Improper handling of batteries can result in explosion, fire or chemical burn due to
leakage.
Do not heat or throw batteries into fire.
Do not reverse polarity, short-circuit or recharge batteries.
Do not deform or disassemble batteries.
Replace batteries only with an identical or equivalent type.
Remove empty batteries immediately and dispose of in an environmentally friendly manner.

1 / 11

82585623

23.07.2019

j0082585623

Summary of Contents for Standard 3361 AL

Page 1: ...ied with batteries in the form of button cells DANGER Batteries can be swallowed This can lead directly to death by suffocation Danger ous substances may cause severe internal burns leading to death within 2 hours Keep new and used batteries away from children Do not use devices if the battery compartment does not close securely and keep away from children If you suspect that a battery has been sw...

Page 2: ... Ceiling mounting on fixed ceilings in appliance box according to DIN 49073 or surface mounted housing see accessories Product characteristics Integrated bus coupling unit 3 PIR sensors Detection field 360 Integrated brightness sensor Deployed as presence detector motion detector or for alert operation Output functions Switching staircase function switching with forced position value trans mitter ...

Page 3: ...ed or brightness threshold exceeded Motion detector function Detection of motions for passageway security in buildings Switch on Motion detection and brightness threshold not reached Switch off No motion in the detection field and run on time elapsed After reacting and switching on the motion detection works independently of the bright ness Alert operation Brightness independent detection of motio...

Page 4: ...ote control If enabled function block 1 can be operated manually by remote control In manual operation brightness and motion detection for function block 1 are switched off until automatic mode is re set Switch on e g light Press the button Switch off e g light Press the Á button Set automatic mode Press the À button Manually changing settings with IR remote control If enabled individual settings ...

Page 5: ...vice has a detection field of 360 The diameter of the detection field depends on the in stallation height and the direction of motion of persons in the detection field Figure 3 The detection field becomes larger the greater the installation height while the detection density and sensitivity are reduced at the same time Figure 3 Detection range depending on the direction of movement Diameter of det...

Page 6: ...led on the ceiling and monitors the sur face below it When used as a motion detector the device is installed e g in the hallway on the ceiling Select a vibration free installation location Vibrations can lead to unwanted switching Avoid interference sources in the detection area Interference sources e g heaters vent ilation air conditioners and cooling light bulbs can lead to unwanted detections I...

Page 7: ...over Using scissors cut out push on cover along the marked lines as required Push on push on cover Aligning the device The device has three independent sensors for motion detection The arrangement of the areas A B and C is clearly evident under the decor ring Figure 6 Figure 5 Detection field areas A B and C installation height 2 50 m Figure 6 Arrangement of the areas A B and C 7 11 82585623 23 07...

Page 8: ...gned correctly when mounting the surface mounted housing on the ceiling Use connecting terminal to connect bus line to the bus connection on the rear side of the device Mount the device correctly in the housing and screw down tightly Attach decor ring 3 6 2 Commissioning Load the address and the application software Switch on the bus voltage Press the programming button 7 The programming LED in th...

Page 9: ... 12 5 mA Connection Bus device connection terminal Ambient temperature 5 45 C Storage transport temperature 25 70 C Relative humidity 5 93 no moisture condensation Protection class III Motion detection Detection angle 360 Range Ø approx 20 m installation height 3 m Brightness sensor Measuring range 0 2000 lx Detection area Ø 2 m Only for Universal version IR remote control Battery type 1 Lithium C...

Page 10: ...h remote control Reduce sensitivity in parameter setting The sensitivity should be reduced by 1 to 2 levels in small spaces Light does not switch off despite sufficient ambient lighting Cause 1 Device is set as motion detector and therefore does not evaluate the ambient lighting after reacting Check programming Set and program device as presence detector Cause 2 Brightness threshold set is too hig...

Page 11: ...Presence detector ALBRECHT JUNG GMBH CO KG Volmestraße 1 58579 Schalksmühle GERMANY Telefon 49 2355 806 0 Telefax 49 2355 806 204 kundencenter jung de www jung de 11 11 82585623 23 07 2019 j0082585623 ...