Application
Ref. no. 2103 REG ES
Page 26
of 44
Description:
Values:
Comment:
→
Measurement - Channel 1
Send measured values cyclically (s)
0
...172800
The following measured values of
Channel 1 can be transmitted cyclically:
Voltage (rms..)
Current (rms..)
Effective power
Reactive power
Setting of the seconds of the cycle time
or switch-off of this function with the
value 0.
Send voltage on change (V)
0
...265
The voltage measured on Channel 1
can be transmitted on changes.
Setting of the voltage change, at which
the measured voltage is transmitted, or
switch-off of this function with the value
0.
Send current intensity on change (0.1
A)
0
...160
The current intensity measured on
Channel 1 can be transmitted on
changes.
Setting of the current intensity change,
at which the measured current intensity
is transmitted, or switch-off of this
function with the value 0.
Send effective power on change (W)
0
...4240
The effective power measured on
Channel 1 can be transmitted on
changes.
Setting of the effective power change,
at which the measured effective power
is transmitted, or switch-off of this
function with the value 0.
Telegram on limit value (Effective
power)
Yes
No
Here, it is possible to set whether a
telegram is transmitted when a limit
value of the effective power measured
on Channel 1 is over or undershot.
Accept limit value from bus
Volatile
Permanent
The limit value for the active power
measured on Channel 1 can be
overwritten with an object.
Setting of whether the new limit value
applies until the next reset / bus voltage
failure or permanently overwrites the
value configured with the ETS.
Limit value (h)
0
..4240
Specification
of
the limit value for the
effective power measured on
Channel 1.