Application
Ref. no. 2103 REG ES
Page 19
of 44
Object Name
Object
function
Type DPT
Flag
29, 52,
75, 98
Ch
n
EC
Total counter level
4 bytes
13.010
CR-T-
Description: The total counter level of the channel in
Wh
. The counter levels "C1 EC" (Object 29), "C2 EC“
(Object 52) and "C3 EC“ (Object 75) are alternating current counters, which only count the energy in a
channel or one phase. By contrast, the counter level "3-phase values EC" (Object 98) counts the total
energy of all three channels or all three phases.
Object Name
Object
function
Type DPT
Flag
30, 53,
76, 99
Ch
n
EC
Reset total counter level
1 bit
1.017
C-W--
Description: The total counter level of the channel is reset on receiving this object. The value of the object
is irrelevant here.
Object Name
Object
function
Type DPT
Flag
31, 54,
77, 100
Ch
n
EC
¼
-hour counter reading
4 bytes
13.010
CR-T-
Description: The counter level attained by the last complete
¼
hour of the
¼
-hour counter of the channel
in
Wh
. The counter levels "C1 EC" (Object 31), "C2 EC" (Object 54) and "C3 EC" (Object 77) pertain to
the alternating current counters, which only count the energy in one channel or one phase. By contrast,
the counter level "3-phase values EC" (Object 100) counts the total energy of all three channels or all
three phases.
Object Name
Object
function
Type DPT
Flag
32, 55,
78, 101
Chn EC
external EV
¼
hour counter reading-LV
4 bytes
13.010
CRWT-
Description: The external limit value of the counter level of the
¼
-hour counter of the channel in
Wh
, at
which, if over or undershot, a monitoring telegram can be transmitted, can be changed using this object.
The new limit value is stored permanently or in the volatile memory, according to the configuration.
Object Name
Object
function
Type DPT
Flag
33, 56,
79, 102
Chn EC LV,
exceed/below
¼-hour counter reading
1 bit
1.xxx
C--T-
Description: If the limit value for the counter level of the
¼
-hour counter of the channel is over or
undershot, a monitoring telegram can be transmitted, whose value is "1" on overshooting or "0" on
undershooting.