Application
Ref. no. 2103 REG ES
Page 39
of 44
Description:
Values:
Comment:
Accept limit value from bus
Volatile
Permanent
The limit value for the
¼
-hour counter
level of the three-phase current
variables can be overwritten with an
object.
Setting of whether the new limit value
applies until the next reset / bus voltage
failure or permanently overwrites the
value configured with the ETS.
Limit value (Wh)
0
...3180
Specification
of
the limit value for the
¼
-hour counter level of the three-phase
current variables.
Hysteresis (Wh)
0
...3180
A hysteresis can be configured for the
over or undershooting of a limit value
for the
¼
-hour counter level of the
three-phase current variables. On
overshooting, the actual limit value is
Limit value +
½
hysteresis
and, on undershooting,
Limit value -
½
hysteresis.
Specification of the hysteresis for the
¼
-hour counter level of the three-phase
current variables.
Counter after ETS download
No reaction
Reset
Here, it is possible to set whether the
counter levels of the three-phase
current variables remain unchanged
after an ETS download or are reset to
0.
Send counter cyclically (s)
0
...172800
The following counter levels of the
three-phase current variables can be
transmitted cyclically:
Counter level
¼
-hour counter level
Counter level, Rate 1
Counter level, Rate 2
Counter level, Rate 3
Setting of the seconds of the cycle time
or switch-off of this function with the
value 0.
1/4-hour counter value cyclic sending
Yes
No
The
¼
-hour counter level of the three-
phase current variables can be
excluded from the cyclical transmission
configured above, in order to reduce
the bus load.