background image

Planning, installation and commissioning of the device are carried out with the aid of KNX-
certified software. Full functionality with KNX commissioning software version ETS3.0d 
onwards.  
An updated version of the product database, technical descriptions and conversion programs 
and other auxiliary programs are available on our Internet website. 

Intended use 

Controlling of luminaires and other applications with DALI operating device in KNX 
installations e.g. electronic ballast 

Installation on DIN rail according to EN 60715 in distribution boxes 

Product characteristics 

Control of up to 64 DALI devices in up to 32 groups 

16 light scenes 

Read out DALI device state via KNX, e.g. brightness or luminaire error 

Manual operation of the DALI groups 

Restraint 

Feedback of switching state and brightness value in bus and manual mode 

Central switching function 

Disabling function for each DALI group 

Separate ON and OFF delay 

Staircase lighting timer with run-on time 

DALI commissioning with ETS plug-in 

Short circuit protection 

Surge protection 

Overload protection 

An individual DALI device can be exchanged during operation without software. 

Delivery state: construction site mode, the DALI groups can be operated using button field. 
All DALI devices are controlled jointly. 

4 Operation 

Operating elements 

picture 2 

(4)  DALI group display (1...32) 
(7)  Button 

c

 – Manual control 

(8)  LED 

c

 – On: Continuous manual mode active 

(9) 

ON/

n

button – switch on or increase brightness 

(10) 

ON/

n

 LED – On: DALI group switched on, brightness 1...100 % 

(11) 

OFF/

o

 button – switch off or dim darker 

(12) LED 

OFF/

o

 – On: DALI group switched on, brightness 0 % 

(13) 

ALL OFF

 buttons – Switch off all DALI groups 

2/8 

82559913 
J:0082559913 

16.08.2010 

DALI gateway 

Summary of Contents for 2097 REG HE

Page 1: ... integral part of the product and must remain with the end customer 2 Device components picture 1 1 Button field for manual control 2 Programming button and LEDs 3 KNX connection 4 DALI group display 5 Connection for mains supply 6 DALI output 3 Function System information This device is a product of the KNX system and complies with the KNX directives Detailed technical knowledge obtained in KNX t...

Page 2: ...straint Feedback of switching state and brightness value in bus and manual mode Central switching function Disabling function for each DALI group Separate ON and OFF delay Staircase lighting timer with run on time DALI commissioning with ETS plug in Short circuit protection Surge protection Overload protection An individual DALI device can be exchanged during operation without software i Delivery ...

Page 3: ...t operation it is not possible to control individual DALI devices i After 5 seconds without a button press the device returns automatically to bus operation Deactivating temporary manual control The device is in short term manual mode o No button press for 5 seconds or o Press c button briefly as many time as necessary until the device leaves the short time manual mode The display 4 is off Switchi...

Page 4: ...s blocked o Activate bus mode see section Deactivating permanent manual control i A blocked DALI group can be operated in manual mode Re enabling DALI groups The device is in continuous manual mode o Press c button briefly as many times as necessary until the display 4 flashes with the desired group o Press buttons ON n and OFF o simultaneously for at least 5 seconds Selected DALI group is enabled...

Page 5: ...s i The DALI control voltage is a functional extra low voltage FELV When performing installation perform the installation in such a way that when an area is disconnected the lines carrying both the DALI and also the mains voltage are disconnected o Connect device as shown in the connection example picture 3 o Connect bus cable with connecting terminal i DALI devices can be connected to various pha...

Page 6: ...e detailed information on commissioning of the DALI system see the technical product information for this device o Load the application software into the device i No programming is possible if no mains voltage is connected 6 Appendix 6 1 Technical data Supply Rated voltage AC 110 240 V Mains frequency 50 60 Hz Power loss max 3 W Ambient conditions Ambient temperature 5 45 C Storage transport tempe...

Page 7: ...evice has not been programmed Program device put DALI system into operation Individual DALI devices have no function Cause 1 Load is defective e g lamp Exchange load Cause 2 DALI device is defective Exchange defective device Switch on voltage Press c and ALL OFF buttons together for at least 10 seconds The device detects the exchanges DALI device and loads in the necessary data The display 4 shows...

Page 8: ... our central customer service office ALBRECHT JUNG GMBH CO KG Service Center Kupferstr 17 19 D 44532 Lünen Service Line 49 0 23 55 80 65 51 Telefax 49 0 23 55 80 61 89 mail vka jung de General equipment Service Line 49 0 23 55 80 65 55 Telefax 49 0 23 55 80 62 55 mail vkm jung de KNX equipment Service Line 49 0 23 55 80 65 56 Telefax 49 0 23 55 80 62 55 mail vkm jung de The Œ symbol is a free trad...