V1.00/EN/00709725 [Thyristor power controller TYA S202]
17
2 Mounting
2.1 Important installation notes
Safety
regulations
k
The choice of cable material, the installation, and the electrical connection
of the device must conform to the requirements of VDE 0100 "Regulations
on the Installation of Power Circuits with Nominal Voltages below AC
1000 V" or the appropriate local regulations.
k
The electrical connection must only be carried out by qualified personnel.
k
An isolating switch should be wired between the voltage supply and the de-
vice to be able to disconnect the device from the voltage supply on all
poles prior to accessing the inner parts of the device.
k
Inside the device, safety clearances meet the requirements for double insu-
lation.
When mounting the connecting cable, ensure that the cables are fitted ac-
cording to regulations and that the safety clearances are maintained.
Fuse protection
k
Fuse protection of the voltage supply in accordance with the VDE regula-
tions must be installed when wiring the voltage supply in the power section.
The supply can also be protected with a circuit-breaker in the supply lead.
The circuit-breaker must correspond to the power consumption of the pow-
er controller.
k
The connecting cables used for the terminals U1, U2, N/L2, V, and L1 must
have an electric strength of AC 500 V.
k
For UL application, it must be ensured that the fuse for the supply protec-
tion of the control electronics is between 2 A and a maximum of 5 A. This
also applies to the fan connection.
k
A semiconductor fuse is installed to protect the power controller in the
event of a ground fault. In the event of a defect, these may only be replaced
with original JUMO semiconductor fuses.
v
Chapter 8.2 "Defekte Halbleitersicherung austauschen"
Wiring
Control cables (SELV potential) must be routed so that they are isolated from
cables with mains voltage potential. For supply protection, fuses (e.g. 2 A,
Neozed type) must also be installed in the control circuit.
Master/slave
1:1 patch cable
Prior to startup, the enclosed 1:1 patch cable must be inserted into the mas-
ter's X8 socket and connected to the slave device's X8 socket.
PE connection
h
A direct protection conductor connection must be provided between the PE
connection terminal on the device and the PE conductor of the supply net-
work.
The cross section of the PE conductor must be at least as large as the cross
section of the voltage supply cables in the power section. In the event that the
protection conductor is not a component of the supply cable or its encase-
ment, the selected conductor cross section may not be less than 2.5 mm
2
(for
mechanical protection) or not less than 4 mm
2
(if the protection conductor is
not protected mechanically).
V
Summary of Contents for TYA S202
Page 8: ...8 V1 00 EN 00709725 Thyristor power controller TYA S202 contents...
Page 23: ...V1 00 EN 00709725 Thyristor power controller TYA S202 23 2 Mounting TYA S202 250A...
Page 52: ...4 Operation 52 V1 00 EN 00709725 Thyristor power controller TYA S202...
Page 66: ...5 Configuration 66 V1 00 EN 00709725 Thyristor power controller TYA S202...
Page 92: ...92 V1 00 EN 00709725 Thyristor power controller TYA S202 9 What to do if...
Page 98: ...10 Technical data 98 V1 00 EN 00709725 Thyristor power controller TYA S202...