7
2 Installation - Electrical Connection
2.1
Identifying the device version
2.2
Excerpt from the technical data
Case
Basic type
702031 Quantrol LC100 (format 48 mm x 48 mm)
702032 Quantrol LC200 (format 48 mm x 96 mm, portrait format)
702034 Quantrol LC300 (format 96 mm x 96 mm)
All types including 1 analog input (universal), 1 binary input (for potential-free con-
tact; can be used as an alternative to analog input 0 to 10 V), 1 relay output (N/O)
Basic type extension
8 Standard, with factory settings
9 Customer-specific programming (on request)
1 2 3 4 Options (3 and 4 not for LC100)
0 0 0 0 -
1 1 1 1 1 relay output (N/O)
2 2 2 2 1 logic output
3 -
-
- 1 analog output (configurable)
- 4 -
- 1 RS485 interface
Voltage supply
23 AC 110 to 240 V +10/-15 %, 48 to 63 Hz
25 AC/DC 20 to 30 V, 48 to 63 Hz
/
-
-
Order code
702034
/ 8 - 3 4 1 2 - 23
Example
Case type
Plastic case for panel mounting as per IEC 61554 (indoor use)
Dimensions (front)
LC100: 48 mm x 48 mm; LC200: 48 mm x 96 mm (portrait format);
LC300: 96 mm x 96 mm
Panel cut-out
LC100: 45 mm x 45 mm; LC200: 45 mm x 92 mm;
LC300: 92 mm x 92 mm
Minimum spacing
horizontal / vertical
LC100: 11 mm / 30 mm (65 mm with USB cable);
LC200/LC300: 22 mm / 30 mm (65 mm with USB cable)
Depth behind panel
LC100: max. 95 mm; LC200/LC300: max. 80 mm
Ambient / storage
temperature range
-5 to +55 °C / -40 to +70 °C
Ambient conditions
rel. humidity < 90% annual average, without condensation