67
8 Appendix
8.1
General technical data
8.1.1
Directives
•
2006/95/EC Low Voltage Directive
•
2004/108/EC Electromagnetic Compatibility Directive
8.1.2
Electrical safety
•
According to DIN EN 61010-1
•
Overvoltage category III, pollution degree 2
8.1.3
Protection type according to DIN EN 60529
•
IP20 modules
•
Multifunction panel on front IP67, on rear IP20
8.1.4
Protection rating
•
Overvoltage category III, pollution degree 2
Protection rating I
(with internal isolation to SELV current circuits)
•
Multichannel controller module
•
Relay module 4-channel
Protection rating III
•
Multifunction panel 840
•
Central processing unit
•
Router module
•
Analog input module 4-channel
•
Analog input module 8-channel
•
Digital input/output module 12-channel
8.1.5
EMC
•
Interference emission: Class A – only for industrial use –
•
Interference immunity: Industry requirement
8.1.6
Voltage supply
•
DC 24 V (19.2 V to 30 V) SELV
•
Residual ripple: 5 %
•
Supply voltage range according to IEC 61131-1 standard: DC 20.4 to 28.8 V