19
7 Installation
7.2
Testing the output signal
7.3
Connection of a HART
®
modem
1
+
+
2
-
-
HART
TEST
+
-
-
+
Supply
voltage
11.5—36 VDC
Burden
1
1
Burden
≤
(U
B
- 11,5 V) / 0.022 A
Burden with HART
®
min. 250
Ω
, max. 1100
Ω
Output signal
test
4 — 20 mA
Test connection via faston connectors 2.8 x 0.8 mm or test termi-
nals.
P
I
+
-
1L+
2L-
up to 15 transmitters
(multidrop mode)
Pressure transmitter
JUMO dTRANS p02
1
Burden
≤
(U
B
- 11.5 V) / 0.022 A
Burden with HART
®
min. 250
Ω
, max. 1100
Ω
HART
®
modem
RS-232-C
PC or note-
book
Burden
1
Supply voltage
11.5 — 36 V DC
Setup
program