10 Configuration level 1
62
10.6 Maths and logic module
This menu is displayed only with enabled maths and logic module.
CONFIG 1
➔
MATHSLOG
Parameter
Value/selection Description
Mathematics 1
➔
MATHS 1
-
Configuration of mathematics as
shown in example “Maths 1” below.
Mathematics 2
➔
MATHS 2
-
Logic 1
➔
LOGIC 1
NO FUNCT
FORMULA
no function
logic formula (setup program)
Logic 2
➔
LOGIC 2
NO FUNCT
FORMULA
no function
logic formula (setup program)
Factory settings are shown
bold
.
CONFIG 1
➔
MATHSLOG
➔
MATHS 1
Parameter
Value/selection Description
Function
➔
FUNCTION
NO FUNCT
DIFFERNC
RATIO
HUMIDITY
FORMULA
no function
difference (a-b)
ratio (a/b)
humidity (a;b)
maths formula
Variable a
➔
VAR A
ANALOG1
...
ANALOG4
MATHS 1
MATHS 2
analogue input 1
...
analogue input 4
mathematics 1
mathematics 2
Variable b
➔
VAR B
ANALOG1
ANALOG2
ANALOG3
ANALOG4
MATHS 1
MATHS 2
analogue input 1
analogue input 2
analogue input 3
analogue input 4
mathematics 1
mathematics 2
Range start
➔
RANGESTRT
-1999.
-1999
to +9999 digit
Range end
➔
RANGEEND
9999.
-1999to
+9999
digit
Definition of a value range for the
result of a mathematical calculation.
If the value range is infringed (above
or below), over/underrange will be
signalled.
v
Section 15.2 “Alarm messages
and display priorities”
Factory settings are shown
bold
.