37
7 Profile program editor
7.2 Editing segments
An existing segment can be edited.
The segment number entry is limited
by the segment that was defined last.
A segment is defined through the
input of a setpoint and a segment
time or gradient.
PGM EDIT
➔
PGM NO.
(1—10)
Parameter
Value/selection Description
Insert segment
Segment number
Segment setpoint
Segment time
Gradient
Operating contact 1
…
Operating contact 8
Minimum limit
of tolerance band
Maximum limit of
tolerance band
Parameter set
number
Repeat cycles
Target segment
➔
SEG INS.
➔
SEG NO.
➔
SETPOINT
➔
SEG TIME
➔
DEGC/MIN
➔
OPCNTCT1
…
➔
OPCNTCT8
➔
TOL.MIN
➔
TOL.MAX
➔
PARA.SET
➔
CYCLES
➔
TARGTSEG
1.
0.
00:00:00
0.
OFF
OFF
-1999.
9999.
1
0.
1.
1
—100
Value within the setpoint limits
00:00:00
—99:59:59
0
—999
ON
OFF
-1999
to 0 (0 = no limiting)
0 to
+9999
(0 = no limiting)
1—2
-1—
0
to +99 (-1 = infinite)
1
—100
Copy segment
Segment number
Target segment
➔
SEG COPY
➔
SEG NO.
➔
TARGTSEG
1.
1.
1
—100
1
—100
Delete segment
Segment number
➔
SEG DEL.
➔
SEG NO.
1.
1
—100
Delete program
➔
PGM DEL.
0.
-1—10 (-1=delete all programs)
factory-set code: 1001
Factory settings are shown
bold
.
H
If the segment time is 0, then the segment will not be accepted.
All digits must be confirmed with
E
.