Technical data
16
JUDO JUKO-LF
1701430 • 2018/11
7
Technical data
Domestic water station
JUDO JUKO-LF ¾" - 2"
The water to be filtered must comply with the European Drinking Water Directive.
Information about:
JUKO-LF
¾"
JUKO-LF 1" JUKO-LF
1¼"
JUKO-LF
1½"
JUKO-LF 2"
Pipe connection
¾"
1"
1¼"
1½"
2"
Backwashing volume
flow
1)
0,3 L/s
0,3 L/s
0,3 L/s
0,3 L/s
0,3 L/s
Rated pressure
PN 16
PN 16
PN 16
PN 16
PN 16
Operating pressure
1,5 - 16 bar 1,5 - 16 bar 1,5 - 16 bar 1,5 - 16 bar 1,5 - 16 bar
Rated flow acc. to
DIN EN 1567
2,3 m³/h
3,6 m³/h
5,8 m³/h
9,1 m³/h
14,0 m³/h
Settable downstream
pressure
1.5 bar -
6 bar
1.5 bar -
6 bar
1.5 bar -
6 bar
1.5 bar -
6 bar
1.5 bar -
6 bar
Factory setting of
downstream pres-
sure
4 bar
4 bar
4 bar
4 bar
4 bar
Mesh size Sieve
insert
0.1 mm
0.1 mm
0.1 mm
0.1 mm
0.1 mm
Water temperature
and ambient temper-
ature
max. 30 °C max. 30 °C max. 30 °C max. 30 °C max. 30 °C
Threaded connection
according to
DIN EN 10226-1
Weight
2,9 kg
3,1 kg
3,4 kg
8,1 kg
8,6 kg
Order no.
8170250
8170251
8170252
8170215
8170216
1) Applies to a fully opened backwash valve and 2 - 3 bar (200 - 300 kPa) mains pressure.