Judo JRSF 1 1/2

JUDO JRSF

7

Installation

4.1.1 Requirements for the place of 

installation

The room where the unit is installed must
be dry and frost free!

Unauthorised persons must not have ac-
cess to the filter!

ATTENTION

(see chapter “Safety information and dan-
gers due to non-compliance”)

The ambient temperature must not ex-
ceed 30°C (86°F)! At higher tempera-
tures or direct sun radiation the material
can be damaged.

In order to be able to safely discharge
the wastewater in operation and in case
of any defects that occur in the system,
precise compliance with the details giv-
en in the “Installation” chapter is neces-
sary! If the wastewater (backwashing)
cannot be safely and completely dis-
charged, the house and installations can
be damaged by water.

A shut-off valve must be installed up-
stream of the filter! This enables the wa-
ter supply to the filter to be interrupted
during installation, servicing/mainte-
nance, repairs and in case of malfunc-
tions. Floods and serious water damage
to house installations can therefore be
avoided.

The unit can be installed in all standard
drinking water pipes.

It is not permitted to install the filter 

upst-

ream of 

the

 

water meter!

4.2

Discharging the
backwashing water

ATTENTION

(see chapter “Safety information and dan-
gers due to non-compliance”)

An adequately dimensioned wastewater
connection (e.g. floor drain) to DIN 1986
must be available for the backwashing wa-
ter. If there is no wastewater connection an
appropriately sized bucket can be used.

The dimensioning depends on the local cir-
cumstances (e.g. wastewater pipe gradient,
number of pipe bends, length of the waste-
water pipe, etc.). The dimensioning must at
least allow all the wastewater to be dis-
charged at the same time. If it is not possible
to provide a wastewater connection directly
beneath the filter, the flushing water can be
fed several metres to the next wastewater
connection, either through a hose or a pipe
to be fitted to the flushing water valve. This
pipe must have the same dimension as the
flushing water valve.

In all options, a free discharge must be en-
sured in accordance with EN 1717.

Summary of Contents for JRSF 1 1/2"

Page 1: ...talling and putting the unit into service These must always be issued to the owner user Extended warranty peri od if a service agreement is concluded Installation and Operating Instructions JUDO JRSF Backwash Protective Filter 1 2 Valid for EU countries and Switzerland Language English Fig JRSF 1 2 Fig JRSF 1 2 ...

Page 2: ...like to thank you for your con fidence in us which you have shown by purchasing this device The product you have purchased is a filter developed us ing state of the art technology This filter is suitable for use in cold drink ing water up to a maximum ambient tem perature of 30 C 86 F It removes coarse and fine grained parti cles larger or equal in size to the filter screen strainer mesh from the ...

Page 3: ...available at the place in which the filter is used This instruction manual is intended to make it easier to familiarize yourself with the filter and its possible intended uses The instruction manual contains important information in order to safely properly and economically run the filter It contains fundamental information which must be observed during installation opera tion and maintenance Obse...

Page 4: ... environment and the unit 1 3 Units used In derogation of the International System of Units SI System International the follow ing units are used 2 Intended Use The installation and operation of the filter is subject to the following existing national reg ulations In addition to the operating instructions and the obliging regulations concerning accident prevention that exist in the country of oper...

Page 5: ... as otherwise the backwashing can be im paired If the filter is not backwashed regu larly a pressure loss can result and this can impair the filter function ATTENTION see chapter Safety information and dan gers due to non compliance In the event of water pressure above 10 bar the pressure reduction valve should be fitted in front of the filter see Fig 1 If the operating pressure is above 10 bar th...

Page 6: ...e ex pected in the drinking water and fulfil the re quirements specified in DIN 19632 Me chanical filters in drinking water installa tions All materials are hygienically and physiologically safe Plastics KTW recom mendations and metallic materials fulfil the requirements of the BgVV German Federal Institute for Consumer Health Protection and Veterinary Medicine 4 Installation 4 1 General ATTENTION...

Page 7: ...oods and serious water damage to house installations can therefore be avoided The unit can be installed in all standard drinking water pipes It is not permitted to install the filter upst ream of the water meter 4 2 Discharging the backwashing water ATTENTION see chapter Safety information and dan gers due to non compliance An adequately dimensioned wastewater connection e g floor drain to DIN 198...

Page 8: ...nce work fill the filter station with water and vent To this end after installation the filter station is filled with water by opening the upstream shut off valve The filter is now at the same pressure as the water system The enclosed air must then be immedi ately removed from the filter station in or der to avoid damage to the installation caused by pressure surges The filter station is vented by...

Page 9: ...ilter Chamber Water Supply Permanent Strainers with Filter and Support Mesh Upper Filter Chamber Multiway Valve Filtered Water Ball Valve for Backwashing Both the degree of soiling and the cleaning process can be observed from the outside All sizes of filter are backwashed with treated water The supply of treated water to the filter station is maintained throughout the back washing process Dirty w...

Page 10: ...he interval until the next backwashing is longer than two months the particles on the filter screen can stick or a large filter pres sure resistance can result Unauthorised persons must not operate the filter Persons who operate the filter must observe the operating instructions Failure to observe these instructions can result in damage to property and personal injuries The smaller the mesh size o...

Page 11: ...nce chapters 5 5 Stoppages ATTENTION see chapter Safety information and dan gers due to non compliance If a filter has to be removed from the flange or unscrewed the chapter Intended use must always be observed Protect the flange surfaces from dam age Damaged flanged surfaces cannot close tight As a result escaping water can damage the building and installa tions Ensure that no dirt can get into t...

Page 12: ...exist Regular servicing is indispensable in order to continue to achieve a successful process for many years after the unit is put into serv ice In the building services sector this is covered by DIN 1988 Part 8 A servicing agreement is the best way to en sure a good operating function beyond the warranty period Wherever possible the regular servicing work and supply with consumables and wearing m...

Page 13: ...mperature 30 C 86 F The water to be filtered must conform to the European Drinking Water Reg ulations Threaded connection to DIN 2999 9 4 Extent of Supply Pre installed Backwash Protective Filter Installation and Operating Instructions Model Order No JRSF 1 8030081 JRSF 1 8030082 JRSF 1 8030076 JRSF 2 8030070 Nominal Pressure Model Operating Pressure Nominal Pressure JRSF 2 1 5 10 bar PN 16 Weight...

Page 14: ...14 JUDO JRSF Spare Parts JRSF 1 2 10 Spare Parts JRSF 1 2 ...

Page 15: ...Disk 2 1607156 1 1607125 1 11 Hand valve 1 1610147 15 1612147 22 12 Threaded flange complete items 13 15 1 2610150 62 2612150 79 13 Threaded flange 1 1610146 51 1612146 66 14 Lip seal 1 1610145 5 1612145 6 15 Scraper ring 1 1610149 6 1612149 7 16 Flat gasket 1 1610144 4 1612144 6 17 Slide valve complete items 9 10 18 22 1 2030056 106 2030057 129 18 Valve spindle 1 1610143 9 1612143 16 19 Head of s...

Page 16: ...be www judo online be JUDO Austria Zur Schleuse 5 A 2000 Stockerau Tel 43 0 2266 6 40 78 Fax 43 0 2266 6 40 79 e mail info judo online at www judo online at Installed by JUDO BIOQUELL SOFT Softener unit reduces water hardness e g to hardness range 2 JUDO JULIA Metering pump for JUL mine ral solution against corrosion brown water and limescale deposits JUDO HEIFI KOM Combination of the heating back...

Reviews: