Installation and operating instructions: JUDO FERROCLEAN sludge separator JFS
2 ½” – 8”
All rights reserved.
JUDO Wasseraufbereitung GmbH
© JUDO Wasseraufbereitung GmbH
Postfach 380
D-71351 Winnenden
Translation into foreign languages and reproduction, even in excerpt form, is only permitted with special
approval.
Tel. +49 (0)7195-692-0
Fax +49 (0)7195-692-188
Revision level: 20.04.2017
E-Mail: [email protected]
judo.eu
21
5.3
Flushing process
5
7
8
2
3
4
6
1
Fig. 7: Flushing process
1
Shut-off valve onsite
5
Bleeding device
2
Shut-off valve onsite
6
Magnesium anode
3
Flushing water shut-off valve
7
Sludge shut-off ball valve
4
Bleeding shut-off valve
8
Magnetic rods
5.3.1
Flushing process with fresh water
Switch off the on-site circulation pump or open the on-site shut-off valve in the bypass.
Close the shut-off valve (1+2) on the inlet and outlet side of the JUDO FERROCLEAN sludge
separator.
Pull all magnetic rods (8) out, up to the base plate of the support legs.
Open the sludge shut-off valve (7).
Open the flushing water shut-off valve (3).
Open the on-site shut-off valve and flush out the sludge until clear water emerges from the channel,
then close the shut-off valve on the customer's site.
Close the flushing water shut-off valve (3).