Installation

3

Installation

CAUTION

The device may only be installed

by qualified technical personnel.

Installation of the device upstream of the

domestic water meter is forbidden.

3.1

Conditions

CAUTION

Risk of property damage or water

damage!
The installation room must be dry

and free from frost.
The ambient temperature must not

exceed 30 °C. In higher temper-

atures or direct sunlight, mater-

ial damage may occur up to and

including breakage of device parts.
The water pressure must not

exceed 7 bar input pressure. With

a water pressure greater than

7 bar, a pressure reducer must be

installed upstream of the device!
An adequately sized wastewater

connection in must be provided in

compliance with DIN 1986.

As per DIN 1988-200, “Water treatment sys-

tems [...] must only be installed in frost-free

areas, in which ambient temperatures of 25

°C are not exceeded.”

Water pressure:

Rated pressure

PN 10

Operating pressure 2 bar - 7 bar

The device works most efficiently at an

operating pressure between 3 bar and

5 bar.

Above water pressures of 5 bar, installa-

tion of a pressure reducer upstream of the

device is recommended.
The water pressure must not fall below

2 bar during operation as otherwise device

functioning may be impaired!

Draining of the waste water:

If a continuous slope to the water trap or

sewer connection (ensuring a free dis-

charge) cannot be achieved at the location

of installation, then a saltwater-resistant

pumping system must be installed to convey

the regeneration waste water

Electrical connection:

Three splash water protected sockets, that

fulfil the legal requirements for wet areas

must be provided on site. The power con-

nection (230 V, 50 Hz) must be continually

live.

Necessary distances:

Rotary flange fitting installation

height (floor to pipe centre):

114.5 cm

Minimum clearance above the

installed softening unit:

30 cm

3.2

Installing the rotary flange fit-

ting on the three-way manifold

The built-in rotary flange serves as a con-

necting element between the domestic

water station and the device. It is suitable

both for horizontal and vertical pipes.

Attention:

 Install the built-in rotary flange

in the flow direction! This is indicated by an

arrow.

INFO_NO_HEADER

The device will not operated if it is

incorrectly installed.

6

JUDO QUICKSOFT MEGA 6  

1703525 • 2022/10

Summary of Contents for 8203525

Page 1: ...Installation manual JUDO QUICKSOFT MEGA 6 Water softening unit Valid for EU countries and Switzerland Language English Read before use and store...

Page 2: ...enden All rights reserved Reprinting even in excerpt form is only per mitted with special approval Dear customers Thank you for the confidence you have shown in us by purchasing this prod uct You have...

Page 3: ...6 3 3 Pipe up system and flush pipe 7 3 4 Connecting the device to pre installed bypass valve 8 3 5 Connecting the softening unit to the salt reservoir 10 3 6 Waste water connection and safety overfl...

Page 4: ...iance with DIN 1986 In order to ensure safe drinking water hygiene a free discharge of the wastewater acc to DIN EN 1717 and DIN 1988 100 must be ensured For the installation of the devices in domesti...

Page 5: ...led with the following symbols Indication of existing dangers Warning of electric voltage Torques specified by the manufac turer User tips and other information Instructions attached directly to the d...

Page 6: ...alla tion of a pressure reducer upstream of the device is recommended The water pressure must not fall below 2 bar during operation as otherwise device functioning may be impaired Draining of the wast...

Page 7: ...R The profiled side of the profile flange seal must point towards the rotary flange fitting see Figure 2 5 Tighten the four hexagon socket head screws UNIT Select the tightening torque about 10 Nm so...

Page 8: ...3 Reclose the shut off valves upstream and downstream of the rotary flange fit ting 3 4 Connecting the device to pre installed bypass valve Initial condition The frame is connected to the now piped up...

Page 9: ...bayonet holes of the bypass valve 6 Turn the device attached to the bypass valve slightly in the clockwise direction to engage the screws in the holes of the bypass valve 7 Tighten the four screws UN...

Page 10: ...w locked position Position the salt reservoir either below or next to the softening unit on the floor ATTENTION Ensure that the jacket hose is run with a constant slope from the softening unit to the...

Page 11: ...988 100 must be ensured Route the waste water hose for the regeneration waste water and the safety overflow hose without kinks to the water trap or to the sewer connection which must ensure a free dis...

Page 12: ...th DIN EN 1717 and DIN 1988 100 Connecting the waste water hoses Shorten the wastewater hoses and lay them without kinks and with a steady slope to the siphon Plug the free ends of the hoses onto the...

Page 13: ...Installation 3 7 Installation example Fig 8 Installation example QUICKSOFT MEGA 6 1703525 2022 10 JUDO QUICKSOFT MEGA 6 13...

Page 14: ...g Detailed information on the commissioning and operation of the water softening system can be found in the operating instructions for the single softener QUICKSOFT MEGA order no 1703519 14 JUDO QUICK...

Page 15: ...s per DIN EN 14743 at 1 bar pressure loss 4 m h Rated flow with a hardness reduction from 360 ppm CaCO3 to 140 ppm CaCO3 6 m h Rated capacity 2 7 mol Total content of all salt reservoirs 150 kg Total...

Page 16: ...vice width with salt reser voirs 1 C 162 Height above the pipe centre D 1145 Height below the pipe centre E 629 Installation depth up to the pipe centre Table 1 All dimensions in mm E1 ca 1000 Install...

Page 17: ...nsions B1 and E1 are variable because the salt reservoirs can be pushed closer or further apart or under the frame 5 2 General error message connection plan Fig 10 General error message connection pla...

Page 18: ...Technical data 5 4 Spare parts Fig 11 Spare parts QUICKSOFT MEGA 6 18 JUDO QUICKSOFT MEGA 6 1703525 2022 10...

Page 19: ...2 Hexagon socket head screws M6x25 set of 4 pieces 1 2060333 5 3 Cover thee way manifold 1 2202233 AU2 1 AU Accounting unit 2 AU not yet specified at the time of going to press Replacement interval 2...

Page 20: ...nline ch judo online ch BENELUX JUDO Wasseraufbereitung GmbH Filiaal Filiale Benelux Laarbeeklaan Av du Laerbeek 72 A1 B 1090 Brussel Bruxelles Phone 32 0 24 60 12 88 Fax 32 0 24 61 18 85 E mail info...

Reviews: