Installation
3
Installation
CAUTION
The device may only be installed
by qualified technical personnel.
Installation of the device upstream of the
domestic water meter is forbidden.
3.1
Conditions
CAUTION
Risk of property damage or water
damage!
The installation room must be dry
and free from frost.
The ambient temperature must not
exceed 30 °C. In higher temper-
atures or direct sunlight, mater-
ial damage may occur up to and
including breakage of device parts.
The water pressure must not
exceed 7 bar input pressure. With
a water pressure greater than
7 bar, a pressure reducer must be
installed upstream of the device!
An adequately sized wastewater
connection in must be provided in
compliance with DIN 1986.
As per DIN 1988-200, “Water treatment sys-
tems [...] must only be installed in frost-free
areas, in which ambient temperatures of 25
°C are not exceeded.”
Water pressure:
Rated pressure
PN 10
Operating pressure 2 bar - 7 bar
The device works most efficiently at an
operating pressure between 3 bar and
5 bar.
Above water pressures of 5 bar, installa-
tion of a pressure reducer upstream of the
device is recommended.
The water pressure must not fall below
2 bar during operation as otherwise device
functioning may be impaired!
Draining of the waste water:
If a continuous slope to the water trap or
sewer connection (ensuring a free dis-
charge) cannot be achieved at the location
of installation, then a saltwater-resistant
pumping system must be installed to convey
the regeneration waste water
Electrical connection:
Three splash water protected sockets, that
fulfil the legal requirements for wet areas
must be provided on site. The power con-
nection (230 V, 50 Hz) must be continually
live.
Necessary distances:
Rotary flange fitting installation
height (floor to pipe centre):
114.5 cm
Minimum clearance above the
installed softening unit:
30 cm
3.2
Installing the rotary flange fit-
ting on the three-way manifold
The built-in rotary flange serves as a con-
necting element between the domestic
water station and the device. It is suitable
both for horizontal and vertical pipes.
Attention:
Install the built-in rotary flange
in the flow direction! This is indicated by an
arrow.
INFO_NO_HEADER
The device will not operated if it is
incorrectly installed.