Solution heat exchanger
The dilute (weak) LiBr solution leaving the lower absorber section is pumped to the generator
section through a solution to solution heat exchanger. It is preheated before entering the
generator section. Such preheating of the dilute solution reduces the driving heat source
requirement in the generator and also helps to cool down the concentrated (strong) solution
before entering the upper absorber section.
Generator
The generator is a falling film design. The steam passes through the stainless steel tubes. There it
heats the preheated dilute solution from the solution heat exchanger and the steam drain cooler.
The refrigerant (water) vapors migrate to the condenser, leaving behind a concentrated (strong)
LiBr solution that is then cooled before being distributed in the upper absorber section.
17
YHAU-C Single Effect Steam-Fired Absorption Chiller
Summary of Contents for York YHAU-C
Page 2: ......
Page 33: ...Figure 11 Location of rupture disk 31 YHAU C Single Effect Steam Fired Absorption Chiller...
Page 103: ...Figure 49 Cooling start diagram 101 YHAU C Single Effect Steam Fired Absorption Chiller...
Page 104: ...Figure 50 Cooling stop diagram YHAU C Single Effect Steam Fired Absorption Chiller 102...
Page 166: ...Figure 73 Steam and drain system YHAU C Single Effect Steam Fired Absorption Chiller 164...
Page 167: ...Figure 74 Duhring diagram PTX chart F 165 YHAU C Single Effect Steam Fired Absorption Chiller...
Page 168: ...Figure 75 Duhring diagram PTX chart C YHAU C Single Effect Steam Fired Absorption Chiller 166...